AMX RDM-3EM Switch User Manual


 
Installation Sheet
RDM-3EM and RDM-6EM Energy Management Modules
The RDM-3EM (FG606-81) and RDM-6EM (FG606-80) are 3 and 6
channel switching energy management modules. They are designed for use
with the RDA series of enclosures in an AMX Lighting™ system.
For more detailed installation and operating instructions, refer to the Radia
Lighting Control System Instruction Manual, available on-line at
www.amx.com.
The RDM-3EM and RDM-6EM are designed with the most advanced
latching energy management relays to support heavy duty commercial
applications, building automation, and loadside management. Equipped
with on-board module microprocessors, both support relay control and
sequencing. Features include:
User selectable delays in sequencing mode to minimize inrush current
and stress on the electrical distribution system.
Selectable strapping facilitates multiple relays on one Radia control
channel for large area control.
Manual on/off override on each relay independent of control system.
Relays retain their state during power and control system outages.
Visual Status Indicators on each relay.
Latching relays do not consume any control current, except when they
change state, eliminating the need for additional Radia power supplies.
Specifications
Dimensions (HW): 10.00" x 2.75" (25.40 cm x 6.99 cm)
Non-phase dependant
Use wires rated at 75°C (167°F)
Torque terminals to 4.4 in lbs.
Wire size: 26 AWG to 10 AWG
Wire stripping length: 0.28" (7 mm)
Weight: 15 oz. (RDM-3EM) and 1.5 lbs. (RDM-6EM)
Included Accessories
4 mounting screws
Control wiring harness
RDM-3EM and RDM-6EM UL and C-Ul Ratings
General purpose: 120, 240, 277, and 347* VAC, 20 A
UL/CUL916 Energy Management Systems.
UL/CUL508 Industrial Control Systems.
Suggested Switched Loads
Incandescent
Fluorescent
Transformer
Low voltage
General purpose
Caution: Pre-Installation Notes
All Class 1 wiring must be connected to proper terminals.
All control wiring must be connected to proper terminals.
Disconnect power while installing or connecting the unit.
Keep top and bottom air vents clear at all times.
Test loads for shorts before connecting.
Use low voltage wires with a 300 volt rating or greater.
Use field installed copper conductors.
All electrical ratings are for continuous duty.
For indoor use only.
FIG. 1
RDM-6EM
Mounting
points
Relays
Sequencing
Delay Jumpers
(JP1 and JP2)
Control
Port
Strapping
Jumpers
(JP3 - JP7)
(1-6)
1
2
3
4
5
6
Mounting points
FIG. 2 RDM-3EM
Mounting
points
Relays
Sequencing
Delay Jumpers
(JP1 and JP2)
Control
Port
Strapping
Jumpers
(JP3 - JP4)
(1-3)
1
2
3
Mounting points
*Agency approval pending