APC AP9218 Switch User Manual


 
MasterSwitch Power Distribution Unit User’s Guide 34
Event-Related Menus and Options
How to Configure Individual Events continued
Event mask
settings
From the evntlist.htm page, to reconfigure actions for an event:
1. Click the link (the current hexadecimal code) for the event.
2. Enter a new hexadecimal code as an event mask to reconfigure
the bits that control the actions for the event
3. Click
Apply.
The bits are numbered
0
to
23
, from left to right.
Note: Bit
5
and bits
14
through
23
are unused. Make sure these bits
are always set to
0
.
Bits
0
to
3
represent the event’s severity:
Bit
4
and bits
6
to
9
enable (
1
) or disable (
0
) event logging
.
and trap
receivers for the event:
Bits 10 to 13 enable (1) or disable (0) e-mail recipients for the event:
Continued on next page
Settings for Bits 0 to 3 Severity
0000 No severity
0001 Informational
0010 Warning
0011 Severe
Bit number Action enabled or disabled for the event
4 Logging the event.
6 Sending traps to Trap Receiver 1
7 Sending traps to Trap Receiver 2
8 Sending traps to Trap Receiver 3
9 Sending traps to Trap Receiver 4
Bit number Action enabled or disabled for the event
10 Sending e-mail to recipient 1
11 Sending e-mail to recipient 2
12 Sending e-mail to recipient 3