Specifications
SU041, SU042-1,
SU042-2
SU045-1 SU043, SU044
Acceptable input voltage 120 VAC:
0 - 165 VAC
208 VAC:
0 - 275 VAC
230 VAC:
0 - 325 VAC
Output voltage
(by default when used with Smart-UPS)
120 VAC:
108 - 132 VAC
208 VAC:
187 - 229 VAC
230 VAC:
207 - 253 VAC
Frequency limits (on-line operation) 47 -63 Hz.
Transfer Times
60 Hz Normal
60 Hz Reduced
50 Hz Normal
50 Hz Reduced
4 ms, typical, 8 ms, maximum
8 ms, typical, 16 ms, maximum
5 ms, typical, 10 ms, maximum
10 ms, typical, 20 ms, maximum
Maximum load 1400 VA: 12A
3000 VA: 24 A
3000 VA: 14 A 1400 VA: 6 A
3000 VA: 13 A
Operating temperature
0 to +50°C (+32 to +122°F)
Storage temperature
-15 to +50°C (+5 to +122°F)
Operating and storage relative humidity 0 to 95%, non condensing
Operating elevation 0 to +3,000 m ( 0 to +10,000 ft)
Storage elevation 0 to +15,000 m (0 to +50,000 ft)
Electromagnetic immunity IEC 801-2, 801-3, 801-4
Audible noise in dBA @ 1 m (3 ft) <45
Size (H x W x D) 4.45 x 43.2 x 19 cm (1.75 x 17.0 x 7.5 in)
Weight - net (shipping) 4.5 (6.8) kg / 10 (15) lb
Safety approvals Listed to UL 1778,
certified to CSA 107.1
GS licensed by VDE
to EN 50091 and
60950
EMC verification FCC Class A certified CISPR 22 Class A