Avocent CCM Network Card User Manual


 
Appendices 103
SpcDeviceOffline
An SPC power control device is offline.
Variables: SPC device location name and CCM appliance port number
SpcDeviceOnline
An SPC power control device is online.
Variables: SPC device location name and CCM appliance port number
SpcLoginErr
The CCM appliance was unable to log in to the SPC device using the username
configured in the appliance.
Variables: SPC device location, CCM appliance port number and username
SpcSocketOff
Command
A command was issued to turn off an SPC device socket.
Variables: username who issued the command, name of server attached to SPC
device socket, SPC device location name, CCM appliance port number and SPC
device socket number
SpcSocketOffSenseFail
An SPC device has detected an off sense failure for a socket. This occurs when a
socket should be in the off state, but is actually in the on state.
Variables: name of server attached to the SPC device socket, SPC device location
name, CCM appliance port number and SPC device socket number
SpcSocketOn
Command
A command was issued to turn on an SPC device socket.
Variables: username who issued the command, name of server attached to SPC
device socket, SPC device location name, CCM appliance port number and SPC
device socket number
SpcSocketOnSenseFail
An SPC device has detected an on sense failure for a socket. This occurs when a
socket should be in the on state, but is actually in the off state.
Variables: name of server attached to the SPC device socket, SPC device location
name, CCM appliance port number and SPC device socket number
SpcSocketReboot
Command
A command was issued to reboot an SPC power control device socket.
Variables: username who issued the command, name of server attached to the SPC
device socket, SPC device location name, CCM appliance port number and SPC
device socket number
SpcStatusSocketOff
An SPC device socket has changed to the off state.
Variables: name of server attached to the SPC device socket, SPC device location
name, CCM appliance port number and SPC device socket number
SpcStatusSocketOn
An SPC power control device socket has changed to the on state.
Variables: name of server attached to the SPC device socket, SPC device location
name, CCM appliance port number and SPC device socket number
SpcTotalLoadHigh
An SPC device has exceeded the maximum threshold for total load amperage.
Variables: SPC device location name and CCM appliance port number
SpcTotalLoadLow
The total load amperage on an SPC device has gone below the minimum threshold.
Variables: SPC device location name and CCM appliance port number
Table C.1: CCM Appliance Enterprise Traps (Continued)
Trap Description and Variable(s)