© 2010 Chromalox
®
, Inc.
Specifications — Table A
* Note: 208V amperage is 86% of 240V value.
† These models can be field changed from single phase to three phase or three phase
to single phase.
Chromalox
®
DIVISION
4
SECTION
SALES
REFERENCE
DATE
SERVICE REFERENCE
PF207
161-305681-001
SEPTEMBER, 2005
(Supersedes PF477-1)
Installation, Operation
and
RENEWAL PARTS IDENTIFICATION
HDS-1 Power Disconnect Switch Kit
for Field Installation in an HVH Series Air Heater
Electrical Data (60 Hz) Standard
Contactor
Model Volts Watts Phase Amps Rating (Qty.)
HVH-02-81 208 2,667 1 12.8
HVH-02-21 208/240 2000/2,667 1 11.1* ——
HVH-02-71 277 2,667 1 9.6
HVH-04-81†
208 4,000
1 19.2 ——
HVH-04-83† 3 11.2 30A (1)
HVH-04-21†
208/240 3,000/4,000
1 16.7* ——
HVH-04-23† 3 9.6* 30A (1)
HVH-04-71 277 4,000 1 14.5 ——
HVH-04-43 480 4,000 3 4.8 30A (1)
HVH-05-81†
208 5,000
1 24.0 ——
HVH-05-83† 3 13.8 30A (1)
HVH-05-21†
208/240 3,750/5,000
1 20.8* ——
HVH-05-23† 3 12.1* 30A (1)
HVH-05-71 277 5,000 1 18.2 ——
HVH-05-43 480 5,000 3 6.0 30A (1)
HVH-07-81†
208 7,500
1 36.1 50A (1)
HVH-07-83 3 20.9 30A (1)
HVH-07-21†
208/240 5,625/7,500
1 31.1* 30A (1)
HVH-07-23 3 18.1* 30A (1)
HVH-07-71 277 7,500 1 27.2 30A (1)
HVH-07-43 480 7,500 3 9.0 30A (1)
HVH-10-81†
208 10,000
1 48.0 50A (1)
HVH-10-83 3 27.8 30A (1)
HVH-10-21†
208/240 7,500/10,000
1 41.7* 30A (1)
HVH-10-23 3 24.0* 30A (1)
HVH-10-43 480 10,000 3 12.0 30A (1)
HVH-12-83 208 12,500 3 34.8 50A (1)
HVH-12-23 208/240 9,375/12,500 3 30.1* 50A (1)
HVH-12-43 480 12,500 3 15.1 30A (1)
HVH-15-83 208 15,000 3 41.8 50A (1)
HVH-15-23 208/240 11,250/13,000 3 36.2* 50A (1)
HVH-15-43 480 15,000 3 18.1 30A (1)
This instruction sheet provides information for field installing an
HDS-1 Power Disconnect Switch in an HVH Series air heater.
ELECTRIC SHOCK HAZARD. Disconnect all power
before installing or servicing heater. Failure to do
so could result in personal injury or property dam-
age. Power Disconnect Switch must be installed by
a qualified person in accordance with the National
Electrical Code, NFPA 70.
GENERAL