Technical Specifications
Single-Phase Model Three-Phase Model
Dimensions Height 5.25 in/13.34 cm 5.25 in/13.34 cm
Width
27.15 in/68.96 cm 27.15 in/68.96 cm
Operating and Performance
Specifications for Power
Enclosures (International)
Depth
17.60 in/44.7 cm 17.60 in/44.7 cm
Weights No hot-plug power supplies
47.5 lb/21.55 kg 47.5 lb/21.55 kg
All hot-plug power supplies
99.5 lb/45.13 kg 125.5 lb/56.93 kg
Input requirements Rated input voltage
200 VAC to 240 VAC 6.25 A at -48 VDC
200 VAC to 240 VAC line
to neutral
Rated input frequency
50 Hz to 60 Hz 50 Hz to 60 Hz
Rated input current per side
24A 20A per phase
Rated input power per side
5760 W 10,552 W
Power cord
1 IEC 309 3-pin, 32A per
side
1 IEC 309 5-pin, 32A per
side
Rated output voltage
-48.8 VDC to -54 VDC -48.8 VDC to -54 VDC
Output voltage
specifications
Rated output current
99A 180A
Rated output power
4798 W 8790 W
Nominal power
4598 W at 208 VAC 8790 W at 230 VAC L-N
Operating
50° to 95° F/10° to 35° C 50° to 95° F/10° to 35° C
Ambient temperature
range (See note)
Shipping
-22° to 140°F/-30° to 60°C -22° to 140°F/-30° to 60°C
Operating
20% to 80% 20% to 80%
Relative humidity,
non-condensing
(See note)
Non-operating
5% to 95% 5% to 95%
Operating 82.4° F/28° C 82.4° F/28° C
Wet bulb temperature
Non-operating
101.7° F/38.7° C 101.7° F/38.7° C
Note: Operating temperature has an altitude derating of 34° F/1° C per 1,000 ft/304.8 m. No direct sunlight. Upper
operating limit is 10,000 ft/3,048 m or 70Kpa/10.1 psia. Upper non-operating limit is 30,000 ft/ 9,144 m or
30.3 KPa/4.4 psia. Storage maximum humidity of 95% is based on a maximum temperature of
113° F/45° C. Altitude maximum for storage is 70 KPa.