Crestron electronic CLX-4HSW4 Switch User Manual


 
Connections via CLT terminal block (sold separately)
LINE 1 - 4: (4) DIN rail terminal blocks, black, line power inputs
SW 1 - 4: (4) DIN rail terminal blocks, red, channel outputs
N IN 1 - 4: (4) DIN rail terminal blocks, white, line input neutrals
N OUT 1 - 4: (4) DIN rail terminal blocks, white, channel output neutrals
Buttons
SETUP: Used for manual channel activation and TSID
LED Indicators
PWR: (green) Indicates line power is applied to the LINE terminal
NET: (yellow) Indicates communication with the control system
1 – 4: (red x4) Indicates state of each channel
SETUP: (red) Indicates unit is in setup/manual mode
Environmental
Temperature: 32° to 104°F (0° to 40°C)
Humidity: 10% to 90% RH (non-condensing)
Heat Dissipation: 16 BTU/Hr + (0.41 BTU/Hr x Load Current in Amps), 42 BTU/Hr at
maximum load
Enclosure
Gray metal with black heat sink, surface mount module with (2) integral mounting flanges,
occupies 1 module space in any CAEN enclosure
Dimensions
Height: 7.59 in (19.27 cm)
Width: 6.92 in (17.57 cm)
Depth: 3.43 in (8.70 cm)
Weight
3.00 lb (1.36 kg)
AVAILABLE ACCESSORIES
CAEN Automation Enclosures
CLT-4HSW4 Terminal Block
www.crestron.com
|
800.237.2041
> 4 independent channels of switching for high-inrush loads
> On/off control of motors, fluorescent, incandescent, low-voltage,
HID, and neon/cold cathode lighting
> Accepts up to 4 separate 120 Volt feeds
> Air-gap relays on every channel output
> Override preset capability
> Occupies 1 module space in a CAEN automation enclosure
> Easy termination using CLT-Series terminal block
As part of a complete Crestron lighting system, the CLX-4HSW4 module provides
4 independent channels of switching for high-inrush loads such as motors, HID
lighting, and fluorescent ballasts, as well as incandescent, low-voltage, and
neon/cold cathode lighting. Each channel is rated for 16 Amps or 1/2 HP, with a
total module rating of 64 Amps when fed from four separate 20 Amp feeds. Air-gap
relays are provided on every channel output allowing individual circuits to be
serviced without disabling the entire module.
An override feature allows each channel to be set to a preset state during setup. In
the event that Cresnet communications should be disrupted for any reason, a
simple contact closure can be used to activate the override presets on a global or
semi-global basis.
The CLX-4HSW4 occupies a single module space in any CAEN automation
enclosure. Termination of high-voltage wiring to the module is facilitated by a
CLT-4HSW4 terminal block, sold separately to enable termination of the wiring
anytime prior to installing the module. CLX modules are controlled by the PAC2
and PAC2M PAC2 professional automation control systems via the Cresnet
network. A 5-wire link provides bussing of the Cresnet and override signals
between modules within an enclosure (interconnect jumpers included).
SPECIFICATIONS
Load Ratings
Switch Channels: 4
Per Channel: 16 Amps, 1/2 HP
Module Total: 64 Amps
Load Types: Incandescent, Fluorescent, Low-voltage, Neon/Cold Cathode, High-Intensity
Discharge (HID), Motors
Power Requirements
120 Volts AC, 60Hz line power
Connections on module
Module Interconnect: (2) 5-pin 0.156 inch headers, Cresnet/Override interconnect ports
Connect to PAC2, PAC2M, CAEN-BLOCK, or adjacent CLX-Series module using interconnect
cable provided
Specifications subject to change without notice. Doc.4848 12/07
©2007 Crestron Electronics, Inc. All brand names, product names and trademarks are the property of their respective owners.
Crestron Electronics, Inc.
15 Volvo Drive
l
Rockleigh, NJ 07647
Tel: 800.237.2041 / 201.767.3400
l
Fax: 201.767.1903
Crestron CLX-4HSW4
4 Channel High-Inrush
Switch Module
Shown with CLT-1DELV4 Terminal Block