Delta Electronics DVP04AD-H2 Switch User Manual


 
Warning
Please read this instruction carefully before use.
Switch off the power before wiring.
DVP04AD-H2 is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust,
humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the device
(e.g. key or specific tools are required to open the enclosure) in case danger and damage on the device may occur.
DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur. Check all
the wiring again before switching on the power.
DO NOT touch any terminal when the power is switched on. DO NOT touch any internal circuit in 1 minute after the
power is switched off.
Make sure the groud terminal is correctly grounded in order to prevent electromagnetic interference.
Introduction
Model Explanation and Peripherals
Thank you for choosing Delta DVP series PLC. DVP04AD-H2 is able to receive 4 points of analog input
signals (voltage or current) and convert them into 14-bit digital signals. Besides, through FROM/TO
instructions in DVP-EH2 MPU program, the data in DVP04AD-H2 can be read or written. There are 49
16-bit control registers (CR) in DVP04AD-H2.
You can select voltage or current output by wiring. Range of voltage output: 10V DC (resolution:
1.25mV). Range of current output: 20mA (resolution: 5µA).
Product Profile (Indicators, Terminal Block, I/O Terminals)
Unit: mm
D - V + I + V +
24V 0V
I + V + I + V + I +
D + COM
8
CH1 CH2 CH 3 CH4RS-485
FG FG FGCOM COM COM
1
DIN rail (35mm)
6
Terminals
2
Connection port for extension modules
7
Mounting hole
3
Model name
8
I/O terminals
4
POWER, ERROR, A/D indicator
9
Mounting port for extension modules
5
DIN rail clip
ENGLISH
External Wiring
C
H
1
1
0
0
K
2
5
0
-10V~
+
1
0
V
V+
I+
C
O
M
CH1
1
0
0
K
C
H
4
1
0
0
K
2
5
0
-20mA~+20mA
V
+
I
+
C
O
M
C
H
4
1
0
0
K
*
5
*
2
A
G
A
G
24+
2
4
-
D
C
/
D
C
+
1
5
V
-
1
5
V
A
G
F
G
F
G
*3
*4
V
o
l
t
a
g
e
i
n
p
u
t
Currentinput
Shieldingcable*1
Shieldingcable*1
C
o
n
v
e
r
t
e
r
Systemgrounding
Earth
(
1
0
0
o
r
l
e
s
s
)
Terminalof
powermodule
*1. When performing analog input, please isolate other power wirings.
*2. If the ripples at the loaded input terminal are too significant that causes noise interference on the wiring, connect the wiring to 0.1
~ 0.47µF 25V capacitor.
*3. Please connect the terminal on both the power modules and DVP04AD-H2 to the system earth point and ground the system
contact or connect it to the cover of power distribution cabinet.
Note: DO NOT wire empty terminals
.
Specifications
Analog/Digital (4A/D) module
Voltage input Current input
Power supply voltage 24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%)
Analog input channel 4 channels/module
Range of analog input ±10V ±20mA
Range of digital conversion ±8,000 ±4,000
Resolution 14 bits (1
LSB
= 2.5mV) 13 bits (1
LSB
= 5µA)
Input impedance 0.5 or lower
Overall accuracy
±0.5% when in full scale (25°C, 77°F)
±1% when in full scale within the range of 0 ~ 55°C, 32 ~ 131°F
Responding time 3ms × the number of channels
Isolation
Internal circuit and analog output terminals are isolated by optical coupler.
No isolation among analog channels.
Range of absolute input ±15V ±32mA
Digital data format 13 significant bits out of 16 bits are available; in 2’s complement
Average function Yes. Available for setting up in CR#2 ~ CR#5; range: K1 ~ K20.
Self-diagnosis Upper and lower bound detection/channel
Communication mode
(RS-485)
ASCII/RTU mode. Communication speed: 4,800/9,600/19,200/38,400/57,600/115,200
bps. ASCII data format: 7-bit, even bit, 1 stop bit (7, E, 1). RTU data format: 8-bit, even
bit, 1 stop bit (8, E, 1). RS-485 cannot be used when connected to PLC MPU.
When connected to DVP-PLC
MPU in series
The modules are numbered
from 0 to 7 automatically by their distance from MPU. No.0 is
the closest to MPU and No.7 is the furthest. Maximum 8 modules are allowed to connect
to MPU and will not occupy any digital I/O points.
Other Specifications
Power supply
Max. rated power consumption
24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%), 2.5W, supplied by external power.
Environment
Operation/storage
Operation: 0°C ~ 55°C (temperature); 50 ~ 95% (humidity); pollution degree 2
Storage: -25°C ~ 70°C (temperature); 5 ~ 95% (humidity)
Vibration/shock immunity
International standards: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27
(TEST Ea)
Control Registers
CR
#
RS-485
parameter
address
Latched
Register content b15
b14
b13
b12
b11
b10
b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
#0
H’4000
R Model name
Set up by the system. DVP04AD-H2 model code = H’6400.
The user can read the model name from the program and see if
the extension module exists.
Reserved CH4 CH3 CH2 CH1
#1
H’4001
R/W
Input mode setting
Input mode: Default = H’0000
Mode 0: Voltage input (-10V ~ +10V)
Mode 1: Voltage input (-6V ~ +10V)
Mode 2: Current input (-12mA ~ +20mA)
Mode 3: Current input (-20mA ~ +20mA)
CR#1: The working mode of the two channels in the analog output module. There are 4 modes for each channel which
can be set up separately. For example, if the user needs to set up CH1: mode 2 (b2 ~ b0 = 010) and CH2: mode 1 (b5 ~
b3 = 001), CR#1 has to be set as H000A and the higher bits (b12 ~ b15) have to be reserved. Default value = H’0000.
#2 H’4002 R/W CH1 average time
#3
H’4003
R/W
CH2 average time
#4
H’4004
R/W
CH3 average time
#5
H’4005
R/W
CH4 average time
Range of settings in CH1 ~ CH4: K1 ~ K20. Default = K10.
Please note that the average time settings at CR#2 ~ CR#5 only
need to be written in once.
#6
H’4006
R CH1 input average
#7
H’4007
R CH2 input average
#8
H’4008
R CH3 input average
#9
H’4009
R CH4 input average
Average of input signals at CH1 ~ CH4
CR#6 ~ CR#9: The average of the signals at CH1~CH4 obtained from the settings in CR#2~CR#5. For example, if the
settings in CR#2~CR#5 is 10, the content in CR#6~CR#9 will be the average of the most recent 10 signals at CH1~CH4.
#12
H’400C
R CH1 input present value
#13
H’400D
R CH2 input present value
#14
H’400E
R CH3 input present value
#15
H’400F
R CH4 input present value
Present value of input signals at CH1 ~ CH4
#18
H’4012
R/W
Adjusted OFFSET value of
CH1
#19
H’4013
R/W
Adjusted OFFSET value of
CH2
#20
H’4014
R/W
Adjusted OFFSET value of
CH3
#21
H’4015
R/W
Adjusted OFFSET value of
CH4
OFFSET settings at CH1 ~ CH4.
Default = K0; Unit: LSB.
When voltage input, range: K-4,000 ~ K4,000
When current input, range: K-4,000 ~ K4,000
CR
#
RS-485
parameter
address
Latched
Register content b15
b14
b13
b12
b11
b10
b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
#24
H’4018 R/W Adjusted GAIN value of CH1
#25
H’4019
R/W
Adjusted GAIN value of CH2
#26
H’401A
R/W
Adjusted GAIN value of CH3
#27
H’401B
R/W
Adjusted GAIN value of CH4
GAIN settings at CH1 ~ CH4.
Default = K4,000; Unit: LSB.
When voltage input, range: K-3,200 ~ K16,000
When current input, range: K-3,200 ~ K10,400
CR#24 ~ CR#27: The adjusted GAIN value of CH1 ~ CH4, representing the analog input voltage or current when the
analog signal is converted into digital value 4,000.
Note: GAIN value – OFFSET value = +800
LSB
~ +12,000
LSB
(voltage) or +800
LSB
~ +6,400
LSB
(current).
When GAIN – OFFSET is small (steep oblique), the resolution of input signal will be finer and variation on the
digital value
will be greater. When GAIN – OFFSET is big (gradual oblique), the resolution of input signal will be rougher and variation
on the digital value will be smaller.
#30
H’401E
R Error status
Register for storing all error status.
See the table of error status for more information.
CR#30: Error status value (see the table below)
Error status Content b15 ~ b8
b7
b6
b5
b4
b3
b2
b1
b0
Abnormal power supply K1 (H’1) 0 0 0 0 0 0 0 1
Incorrect mode setting K4 (H’4) 0 0 0 0 0 1 0 0
OFFSET/GAIN error K8 (H’8) 0 0 0 0 1 0 0 0
Hardware malfunction K16 (H’10) 0 0 0 1 0 0 0 0
Abnormal digital range K32 (H’20) 0 0 1 0 0 0 0 0
Incorrect average times setting K64 (H’40) 0 1 0 0 0 0 0 0
Instruction error K128 (H’80)
Reserved
1 0 0 0 0 0 0 0
Note: Each error status is determined by the corresponding bit (b0 ~ b7) and there may be more than 2 errors occurring at the
same time. 0 = normal; 1 = error.
#31
H’401F
R/W
Communication address
setting
For setting RS-485 communication address.
Range: 01 ~ 254. Default = K1.
#32
H’4020
R/W
Communication speed (baud
rate) setting
For setting up communication speed: 4,800/9,600/19,200/
38,400/57,600/115,200 bps. ASCII data format: 7-bit, e
ven bit, 1
stop bit (7, E, 1). RTU data format: 8-bit, even bit, 1 stop bit (8,
E, 1). Default = H’0002.
b0: 4,800 bps. b1: 9,600 bps (Default).
b2: 19,200 bps. b3: 38,400 bps.
b4: 57,600 bps. b5: 115,200 bps
b6 ~ b13: Reserved.
b14: High/low bit exchange of CRC checksum (only valid in
RTU mode).
b15: Switch between ASCII/RTU mode; 0 = ASCII mode
(Default).
Reserved CH4 CH3 CH2 CH1
#33
H’4021 R/W
Returning to default setting;
OFFSET/GAIN tuning
authorization
Default = H’0000. Take the setting of CH1 for example:
1. When b0 = 0, the user is allowed to tune CR#18 (OFFSET)
and CR#24 (GAIN) of CH1. When b0 = 1, the user is not
allowed to tune CR#18 and CR#24 of CH1.
2. b1 represents whether the OFFSET/GAIN tuning registers
are latched. b1 = 0 (default, latched); b1 = 1 (non-latched)
3. When b2 = 1, all settings will return to default values.
CR#33: For authorizations on some internal functions, e.g. OFFSET/GAIN tuning. The latched function will store the
output setting in the internal memory before the power is cut off.
#34
H’4022
R Firmware version
Displaying the current firmware version In hex; e.g. version 1.0A
is indicated as H’010A.
#35 ~ #48 For system use
Symbols:
: Latched (when written in through RS-485 communication);
: Non-latched;
R: Able to read data by FROM instruction or RS-485 communication;
W: Able to write data by TO instruction or RS-485 communication.
LSB (Least Significant Bit):
For voltage input: 1
LSB
= 10V/8,000 = 1.25mV. For current input: 1
LSB
= 20mA/4,000 = 5µA.
CR#0 ~ CR#34: The corresponding parameter addresses H’4032 ~ H’4022 are for users to read/write data by
RS-485 communication. When using RS-485, the user has to separate the module with MPU first.
a. Communication baud rate: 4,800/9,600/19,200/38,400/57,600/115,200 bps.
b. Modbus ASCII/RTU communication protocols: ASCII data format (7-bit, even bit, 1 stop bit (7, E, 1)); RTU
data format (8-bit, even bit, 1 stop bit (8, E, 1)).
c. Function: H’03 (read register data); H’06 (write 1 word datum to register); H’10 (write many word data to
register).
d. Latched CR should be written by RS-485 communication to stay latched. CR will not be latched if written
by MPU through TO/DTO instruction.
Adjusting A/D Conversion Curve
Voltage input mode:
CR#1 mode 0 GAIN = 5V (4,000
LSB
). OFFSET = 0V (0
LSB
).
CR#1 mode 1 GAIN = 6V (4,800
LSB
). OFFSET = 2V (1,600
LSB
).
GAIN
The voltage input value when the digital output value =
K4,000.
Range: -3,200
LSB
~ +16,000
LSB
.
OFFSET
The voltage output value when the digital input value = K0.
Range: -4,000
LSB
~ +4,000
LSB
.
+
8
,
0
0
0
+
4
,
0
0
0
-
4
,
0
0
0
1
0
V
-
8
,
0
0
0
-6V-10V
6V
2V
0
GAIN
OFFSET
D
i
g
i
t
a
l
o
u
t
p
u
t
V
o
l
t
a
g
e
i
n
p
u
t
M
o
d
e
0
M
o
d
e
1
5
V
GAIN - OFFSET Range: +800
LSB
~ +12,000
LSB
.
Current input mode:
CR#1 mode 2 GAIN = 12mA (2,400
LSB
). OFFSET = 4mA (800
LSB
).
CR#1 mode 3 GAIN = 10mA (2,000
LSB
). OFFSET = 0mA (0
LSB
).
GAIN
The current input value when the digital output value =
K2,000.
Range: -3,200
LSB
~ +10,400
LSB
.
OFFSET
The current input value when the digital output value = K0.
Range: -4,000
LSB
~ +4,000
LSB
.
+4
,000
-
4
,0
0
0
-12
m
A-20
A
4m
A
0
O
FFSE
T
20m
A
G
A
IN
D
i
g
ita
l
o
utp
u
t
Currentinput
M
o
d
e
3
Mode2
GAIN - OFFSET Range: +800
LSB
~ +6,400
LSB
.
The user can adjust the OFFSET/GAIN curves according to the actual needs by changing the OFFSET value
(CR#18 ~ CR#21) and GAIN value (CR#24 ~ CR#27).
(OPEN TYPE) /
DVP DVP04AD-H2 4
14 DVP-EH2 FROM/TO
49 CR (Control Register) 16 bits
±10V DC 1.25mV
±20mA 5µA
mm
D - V + I + V +
24V 0V
I + V + I + V + I +
D + COM
8
CH1 CH2 CH3 CH4RS-485
FG FG FGCOM COM COM
1
DIN (35mm)
6
2
/
7
3
8
4
9
/
5
DIN
CH1
100K
250
*1
-10V~+10V
V+
I+
COM
CH1
100K
CH4
100K
250
*1
-20mA~+20mA
V+
I+
COM
CH4
100K
*5
*2
AG
AG
24+
24-
( 100 )
DC/DC
+15V
-15V
AG
FG
FG
*3
*4
*1
*2 0.1 ~ 0.47µF 25V
*3 DVP04AD-H2
/ (4A/D)
24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%)
4 /
±10V ±20mA
±8,000 ±4,000
14 bits (1
LSB
= 2.5mV) 13 bits (1
LSB
= 5µA)
200K 250
±0.5% (25°C, 77°F) ±1% (0 ~ 55°C, 32 ~ 131°F)
3ms ×
±15V ±32mA
16 13 bits
CR#2 ~ CR#5 K1 ~ K20
/
(RS-485)
ASCII/RTU (4,800/9,600/19,200/38,400/57,600/115,200 bps) ASCII
7-bit 1 stop bit (7, E, 1) RTU 8-bit
1 stop bit (8, E, 1) PLC RS-485
DVP-PLC 0 7 8 I/O