Delta Electronics DVP-EC3 Switch User Manual


 
Warning
This instruction sheet provides only information on the electrical specification, general functions, installation and
wiring. The program design and applicable instructions for DVP-EC3 are the same as those applicable for DVP-ES
series. For detailed information, please refer to “DVP-PLC Application Manual: Programming”. For details of the
optional peripheral, please refer to the instruction sheet enclosed in it.
DVP-EC3 series PLC is an OPEN TYPE device and therefore should be installed in an enclosure free of airborne
dust, humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the
device (e.g. key or specific tools are required for operating the enclosure) in case danger and damage on the device
may occur.
DO NOT connect the input AC power supply to any of the I/O terminals; otherwise serious damage may occur. Check
all the wiring again before switching on the power. Make sure the ground terminal is correctly grounded in order
to prevent electromagnetic interference.
Introduction
Thank you for choosing Delta DVP-EC3 series programmable logic controller. DVP-EC3 currently offers 10-16
I/O points. To ensure proper installation, operation and maintenance, please read this instruction sheet carefully
and provide users with this instruction sheet before installing DVP-EC3.
Product Profile & Outline
+24 V24GS/ SX0X1X2X3X4X5X6X7
LN C0Y0Y1Y2Y3C1Y4Y5
POWE R
RUN
ERRO R
DVP 16EC
8DI-DC / 8 DO-R
Direct m ounting hole
Input po ints Indication
DC power su pply output
I/O point indicators
COM 1 Com munication
(RS-232C)port
DIN rail (35mm)
Direct mounting hole
Fixed I/O terminals
DIN rail clip
POW ER, RU N & ER ROR indicators
Output points Indication
AC power supply input
COM 2 Com munication
(RS-485)port
D+D-SG
Y6Y7
Model name
COM2
COM1
Dimensions
90.5mm
95 mm
48.5mm
90m m
99 mm
+24V 24G S/S
X0
X1X2
X3
X4
X5X6
X7
IN
OUT
POW ER
RUN
ER ROR
L N C0Y0Y1Y2Y3C1Y4Y5
DVP 16EC
8DI-DC / 8DO-R
INPU T
AC 1 00~2 4 0V
0123 456 7
0123 4
5
6
7
D+D-SG
Y6Y7
COM2
COM1
ENGLISH
Specifications
Model
Item
DVP10EC00 3 DVP14EC00 3 DVP16EC00 3
Power supply voltage 100 ~ 240V AC (-15% ~ 10%), 50/60Hz ± 5%
Operation
DVP-EC3 starts to run when the power supply rises to 95 ~ 100V AC and stops
when the power supply drops to 70V AC. It continues to run for 10ms after the
power supply is cut off.
Power supply fuse 2A/250V AC
Power consumption 9VA
DC24V Supply Current 100mA
Power supply protection DC24V output short circuit protection
Voltage withstand
1,500V AC (Primary-secondary), 1,500V AC (Primary-PE), 500V AC
(Secondary-PE)
Insulation resistance > 5M at 500V DC (between all I/O points and earth)
Noise immunity
ESD: 8KV Air Discharge
EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 250V
RS: 26MHz ~ 1GHz, 10V/m
Earth
The diameter of grounding wire shall not be less than that of L, N terminal of the
power supply. (When many PLCs are in use at the same time, please make sure
every PLC is properly grounded.)
Operation/storage
Operation: 0°C ~ 55°C (temperature), 50 ~ 95% (humidity), Pollution degree2
Storage: -25°C ~ 70°C (temperature), 5 ~ 95% (humidity)
Vibration/shock
resistance
International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/ IEC61131-2 & IEC
68-2-27 (TEST Ea)
RS-485 communication
mode
Not supported Not supported Supported
Weight (g) R: 192g; T: 180g R: 202g; T: 185g R: 212g; T: 190g
Input Point
Input point type Digital Input
Input type DC (SINK or SOURCE)
Input current 24V DC 5mA
Off On, > 15V DC
Action level
On Off, < 5V DC
Reaction time
(Conversion sampling
time)
Approx. 10ms (0 ~ 20ms adjustable in D1020)
Output Point
Output point type Relay-R Transistor-T
Current specification 2A/1 point (5A/COM) 0.5A/1 point (2A/COM)
Voltage specification < 250V AC, 30V DC
5 ~ 30V DC
(UP, ZP must work wit external
auxiliary power supply 24V DC -15%
~ +20%, rated consumption approx.
1mA/point)
75VA (inductive)
Maximum load
90W (resistive)
15W/1 point (Resistive)
Reaction time Approx .10ms Off On 30us, On Off 100us
Installation & Wiring
3.1 I/O Terminal Layout
DVP10EC00R3/T3
X4X3X2X1X0
S/S
24G
+24V
X5
Y3
Y2Y1Y0C0
DVP10EC00R3 (6DI-DC / 4DO-R)
X4X3X2X1X0S/S
24G
+24V
X5
Y3
Y2Y1Y0ZPUP
DVP10EC00T3 (6DI- DC / 4DO-T)
DVP14EC00R3/T3
X4X3X2X1X0
S/S
24G+24V
X7X6X5
Y4C1Y3Y2Y1Y0C0 Y5
DVP14EC00R3 (8DI-DC / 6DO-R)
X4X3X2X1X0S/S
24G+24V
X7X6X5
Y4Y3Y2Y1Y0ZPUP Y5
DVP14EC00T3 (8DI-DC / 6DO-T)
DVP16EC00R3/T3
X4X3X2X1X0
S/S
24G
+24V
X7X6X5
Y4C1Y3Y2Y1Y0C0 Y5
DVP16EC00R3 (8DI-DC / 8DO-R)
Y6
Y7
SG
D-D+
X4X3X2X1X0
S/S
24G
+24V
X7X6X5
Y4Y3Y2Y1Y0ZPUP Y5
DVP16EC00T3 (8DI-DC / 8DO-R)
Y6
Y7
SG
D-D+
1. Use the 12-24 AWG single-core bare wire or the multi-core wire for the I/O wiring, and please use 60/75°C
copper conductor only. The twisting power of the screw for the DVP-EC3 terminal is 3.80 kg-cm (3.30
lb-in) .
2. DO NOT wire empty terminal. DO NOT place the input signal wire and output power wire in the same
wiring circuit.
3. DO NOT drop tiny metallic conductor into DVP-EC3 while screwing and wiring
3.2 Mounting & Installation
Please install PLC in an enclosure with sufficient space around it to allow heat dissipation. For heat
dissipation, make sure to provide a minimum clearance of 50mm between the unit and all sides of the cabinet.
(See the figure.)
How to screw: Please use M4 screw according to the dimension of the product.
How to install DIN rail: PLC can be secured to a cabinet by using the 35mm DIN rail. When mounting PLC to
DIN rail, be sure to use the end bracket to stop any side-to-side movement of it and reduce the change of
wires being loosen. A small retaining clip is at the bottom of it. To secure PLC to DIN rail, place the clip onto
the rail and gently push it up. To remove it, pull the retaining clip down and gently remove it from DIN rail.
3.3 Wiring Notes
Specification & Wiring of Power Supply
The power supply input for DVP-EC3 model is AC input. When operating DVP-EC3, please make sure that:
1. The input voltage should be 100 ~ 240VAC. The power supply should be connected to L and N terminals.
Please note that wiring AC110V or AC220V to +24V output terminal or digital input points will result in
serious damage on it.
2. Use 1.6mm wire (or longer) for the grounding of it.
3. The power shutdown of less than 10ms will not affect the operation of it. However, power shutdown time
that is too long or the drop of power supply voltage will stop the running of it, and all outputs will go “OFF”.
When the power supply turns normal again, DVP-EC3 will automatically return to its operation. (Please be
aware of the latched auxiliary relays and registers inside DVP-EC3 when programming.)
4. For max. output of the +24V power supply output terminal for each model, please refer to the electrical
specification table. DO NOT connect other external power supplies to this terminal. Every input point
requires 5 ~ 7mA to drive (e.g. 16 input points will require 80 ~ 112mA to drive). The +24V input on DVP-
EC3 is only for digital input points; other external loads are not suggested.
L
100~240VAC
N
24G S/S X0 X1 X2
2.0A
DC/DC
5V
+24V
Safety Wiring
Since DVP-EC3 controls many devices, actions of any device may affect actions of other devices, and the
breakdown of any one device may cause the breakdown of the entire auto-control system and danger.
Therefore, we suggest you wire a protection circuit at the power supply input terminal, as shown in the figure
below.
1
AC power supply load
2
Power supply circuit protection fuse (3A)
3
POWER indicator
4
Emergency stop: This button can cut off the system
power supply when accidental emergency takes place
5
Breaker
6
DVP-EC3 (main processing unit)
7
Earth resistance: < 100
8
Power supply: 100 ~ 240V AC, 50/60Hz
I/O Point Wiring
The input signal of the input point is the DC power DC input. There are two types of DC type wiring: SINK and
SOURCE, defined as follows:
Input Point Loop Equivalent Circuit & Wiring
DC Signal IN
(SINK mode)
+24V
24G
S/ S
X0
+5 V
24VD C
X1
DC Signal IN
(
SOURCE mode)
+24V
24G
S/S
X0
+5V
24VDC
X1
Below is an example. For detailed point configuration, please refer to specifications of each model:
Relay (R) Output Circuit Wiring
1
Flywheel diode: To extend the life span of contact
2
Emergency stop: Uses external switch
3
Fuse: Uses 5 ~ 10A fuse at the shared terminal of
output contacts to protect the output circuit
4
Varistor: To reduce the interference on AC load
5
Empty terminal: Not in use
6
DC power supply
7
Neon indicator
8
AC power supply
9
Incandescent light (resistive load)
10
Manually exclusive output: Uses external circuit and
forms an interlock, together with DVP-EC3 internal
program, to ensure safety protection in case of any
unexpected errors.
Transistor (T) Output Circuit Wiring
1
DC power supply
2
Emergency stop
3
Circuit protection fuse
4
The output of the transistor model is “open
collector”. If Y0/Y1 is set to pulse output, the output
current has to be 0.05 ~ 0.5A to ensure normal
operation of the model.
5
Manually exclusive output: Uses external circuit and
forms an interlock, together with DVP-EC3 internal
program, to ensure safety protection in case of any
unexpected errors.
DVP-ES DVP-PLC
(OPEN TYPE)
DVP-EC3 DVP-EC3 10 ~ 16
COM1
+24V
24GS/S
X0X1X2X3X4X 5X6X7
LN C0Y0Y1Y2Y3 C1Y4Y5
POWER
RUN
ERROR
DV P1 6EC
8DI-DC / 8DO-R
DIN (3 5mm)
(RS-232C )
DIN
COM 2 (RS- 485 )
D+
D-
SG
Y6Y7
CO M1
CO M2
90.5mm
95 mm
48.5mm
90m m
99 mm
+24V 24G S/SX0X1X2X3X4X5X6X7
IN
OUT
POW ER
RUN
ER ROR
L N C0Y0Y1Y2Y3C1Y4Y5
DVP 16EC
8DI-DC / 8DO-R
INPU T
AC 1 00~2 4 0V
01 234 56 7
0123 45
6
7
D+D-SG
Y6Y7
COM2
COM1
DVP10EC00 3 DVP14EC00 3 DVP16EC00 3
100 ~ 240V AC (-15% ~ 10%), 50/60Hz ± 5%
95 ~ 100V AC DVP-EC3 70V AC DVP-EC3
10ms
2A/250V AC
9VA
DC24V
100mA
DC24V
1,500V AC (Primary-secondary)
1,500V AC (Primary-PE)
500V AC (Secondary-PE)
5M / 500V DC
ESD: 8KV Air Discharge
EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 250V
RS: 26MHz ~ 1GHz, 10V/m
L, N PLC
/
0°C ~ 55°C 50 ~ 95% 2
-25°C ~ 70°C 5 ~ 95%
/ IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea)
RS-485
,g R 192g T 180g R 202g T 185g R 212g T 190g
SINK SOURCE
24VDC 5mA
Off On 15V DC
On Off 5V DC
10ms D1020 0 ~ 20ms
-R -T
2A/1 5A/COM 0.5A/1 2A/COM
250V AC, 30V DC
5~30VDC
(UP, ZP 24V DC -15% ~ +20%
1mA/ )
75VA
90W
15W/1
10ms Off On 30us On Off 100us