Delta Electronics DVP-SX Network Card User Manual


 
Warning
This Instruction Sheet only provides descriptions for electrical specifications, general specifications, installation &
wiring, troubleshooting and peripherals. Other detail information about programming and commands is compatible
with SA/SC/SX series; please see PLC Application Manual. For more information about the optional peripheral,
please see individual product manual.
This is an OPEN TYPE PLC. The PLC should be kept in an enclosure away from airborne dust, humidity, electric
shock risk and vibration. Also, it is equipped with protective methods such as some special tools or keys to open the
enclosure, so as to avoid the hazard to users and the damage to the PLC.
Never connect the AC main circuit power supply to any of the input/output terminals, as it will damage the PLC.
Check all the wiring prior to power up. To avoid any electromagnetic noise, make sure the PLC is properly
grounded . DO NOT touch terminals when power on.
Introduction
Thank you for choosing DELTA’s PLC DVP series. The DVP-SX series is a 10-point (4DI+2DO+2AI+2AO)
special main processing unit. Besides the same commands and functions as DVP-SA/SX/SC series, 2-CH
12-bit analog voltage/current input and 2-CH 12-bit analog voltage/current output are all bipolar. There is
built-in 2-digit 7-segment display corresponds to internal register directly to display PLC station or
user-defined code.
Product Profile and Outline
1
Status indicator: POWER, RUN,
ERROR, BAT.LOW
2
RUN/STOP switch
3
2-digital 7-segment display
4
Digital I/O terminal
5
DIN rail clip
6
Analog I/O terminals
7
I/O point indicators
8
COM1 (RS-232) (Rx) indicator
9
COM2 (RS-485) (Tx) indicator
10
COM1 (RS-232)
Communication port (Slave)
Units: mm
11
Nameplate
12
Expansion port
13
Mounting hold of the expansion
unit
14
DIN rail (35mm)
15
Expansion unit clip
16
COM2 (RS-485)
Communication port
17
DC Power input
18
2 pin removable terminal
(standard accessory)
19
Power input cable
(standard accessory)
20
Battery Cover
21
Battery socket connection
Battery replacement: Please change the battery within 3 minutes, or the
internal data of the PLC (including the program area, RTC and latched
registers) could be lost or destroyed.
22
Battery mount
ENGLISH
Electrical Specifications
Electrical Specifications
Model
Item
DVP10SX11R/T
DVP08SM11N DVP08SN11R/T
DVP08SP11R/T
DVP16SP11R/T
Power supply voltage
MPU: 24V DC (-15% ~ 20%) (with DC input reverse polarity protection),
Expansion Unit: supplied by the MPU
Fuse 2A / 250V AC -
Power Consumption 5W 1W 1.5W 1.5W 2W
Insulation Resistance
> 5 M at 500 V DC (Between all inputs / outputs and earth)
Noise Immunity
ESD: 8KV Air Discharge
EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 250V
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS: 26MHz~1GHz, 10V/m
Grounding
The diameter of grounding wire cannot be smaller than the wire diameter of terminals L and N
(All DVP units should be grounded directly to the ground pole).
Environment
Operation: 0°C ~ 55°C (temperature), 50 ~ 95% (humidity), Pollution degree 2;
Storage: -25°C ~ 70°C (temperature), 5 ~ 95% (humidity); D/A output operation: 0°C ~ 50°C
(temperature)
Vibration / Shock
Resistance
Standard: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea)
Weight (approx.) (g) 138 / 133 64 88 / 68 90 / 70 96 / 76
Approvals
Electrical Specification of Input Point Electrical Specification of Output Point
Input Type DC (SINK or SOURCE) Output Type
Relay-R Transistor-T
Input Current 24V DC 5mA
Current
Specification
1.5A/1 point
(5A/COM)
0.3A/1 point @ 40°C; When the output of Y0
and Y1 is high-speed pulse, Y0 and Y1 =
30mA
Off On,
X0,X1: above 18.5V DC
X2,X3: above 16.5V DC
Voltage
Specification
Below 250V
AC, 30V DC
30V DC
Active Level
On Off,
X0~X3 below 8V DC
75VA
(Inductive)
Maximum
Loading
90 W
(Resistive)
9W/1 point
When the output of Y0 and
Y1 is high-speed pulse, Y0
and Y1 = 0.9W (Y0 = 32
kHz,
Y1 = 10kHz)
Responding
Time
About 10ms (An
adjustment range of 0 ~ 20
ms could be selected
through D1020 and D1021)
Responding
Time
About 10 ms
Off On 20us
On Off 30us
Y0 and Y1 are specified
points for high-speed pulse
Model Name & I/O Configuration
Input Output
Point
Type Point
Type
Model Power
DI
AI
DI AI DO
AO
DO AO
DVP10SX11R
4
2
2
2
Relay
DVP10SX11T
24V
DC
+20%
-15%
4
2
DC24V/5 mA
Sink or Source
-20 ~ 20mA
range(-1,000 ~ +1,000)
-10 ~ +10V
range(-2,000 ~ +2,000)
2
2
Resistor
-20 ~ 20mA
(range:-2,000 ~ +2,000)
-10 ~ +10V
(range:-2,000 ~ +2,000)
Installation & Wiring
3.1 PLC Mounting Arrangements and Wiring Notes
Installation of the DIN rail:
The DVP-PLC can be secured to a cabinet by using the
DIN rail that is 35mm high with a depth of 7.5mm. When
mounting the PLC on the DIN rail, be sure to use the
end bracket to stop any side-to-side motion of the PLC,
thus to reduce the chance of the wires being pulled
loose. At the bottom of the PLC is a small retaining clip.
To secure the PLC to the DIN rail, place it onto the rail
and gently push up the clip. To remove it, pull down the
retaining clip and gently pull the PLC away from the DIN
rail. As shown on the right:
When installing the DVP series
PLC, make sure that it is
installed in an enclosure with
sufficient space (as shown
below) to its surroundings so as
to allow heat dissipation.
DVP
MP
D
D
DD
D > 50 mm
Wiring:
22-16AWG
< 1.5mm
1. Please use 22-
16AWG (1.5mm) wiring (either single or multiple core) for
I/O wiring terminals. The specification for the terminals is as shown on
the left. PLC terminal screws should be tightened to between 1.95
kg-cm (1.7 in-lbs). Use 60/75°C copper conductor only.
2. I/O signal wires or power supply should not run through the same
multi-wire cable or conduit.
3.2 Wiring Notes
Power Input Wiring
DVP-SX series input power supply is DC input. Please take a note of listed items when operating DVP-SX.
Series.
1. Please make sure the power is at terminals 24V DC and 0V (power range is 20.4V DC ~ 28.8V DC). When
voltage is lower than 20.4V DC, PLC will stop operating, all outputs will turn Off and ERROR LED will flash
continuously.
2. If the power-off time is less than 10ms, the PLC still operates unaffectedly. If the power-off time is too long or
the power voltage drops, the PLC will stop operating and all the outputs will be Off. Once the power is
restored, the PLC will return to operate automatically. (There are latched auxiliary relays and registers
inside of the PLC, please be aware when programming.)
DC Input Type
S/S
X0 X1 X2OV24VDC
DC/DC
2A
5V
20.4V~28.8V
Safety Wiring
Since the PLC is in control of numerous devices, motion of either one device could affect the motion of other
devices,
therefore
the breakdown of either one device would consequently be detrimental to the whole auto
control system, and danger will thus be resulted. Please use the recommended wiring below for the power
input:
Power supply for AC loads
Power Circuit Protection Fuse (3A)
Power On pilot indicator
Emergency stop
The machinery must provide a quick manual method
disconnecting all system power.
Circuit isolation device (System Power Disconnect)
Utilize the electromagnetic contactor and the relay to be the
isolation unit of the power circuit to prevent the possible
instability of the system when the power is supplied on and off.
DVP PLC MPU (main processing unit)
Grounding
MC
MC
NL
1
1
2
3
4
5
6
8
Gu ard
Li mit
7
MC
Power supply:
AC: 100 ~ 240V AC, 50/60Hz
DC: 24V DC
Input Point Wiring
The input signal of the input point is the DC power DC input. There are two modes of DC type wiring: SINK and
SOURCE, defined as follows:
Sink = Current flows into the common terminal S/S Source = Current flows out of common terminal S/S
Sinking
S/S
X0
Sourcing
S/S
X0
Loop Equivalent Circuit of Input Point Wiring Loop
DC Type
(DC Signal IN)
SINK Mode
+24V
24G
S/S
X0
24VD C
SIN K
+5V
+24V OV
Sin k Type
X1
X2
S/S
X0
24V DC
Loop Equivalent Circuit of Input Point Wiring Loop
DC Type
(DC Signal IN)
SOURCE Mode
+24V
24 G
S/ S
X0
24 VDC
SOU RC E
+5V
So urce Type
X1
X2
S/S
X0+24V OV
24V DC
Output Point Wiring
Y0
RY
LED
C0
RE LAY O UTP UT
LO AD
PO WE R
DVP-**-**-11-R
Y0
LED
C0
TRAN SISTOR OUTPUT
LOAD
DVP- **-**-11-T
<0 .3A
T
R
G
1. There are two kinds of DVP-SX Series PLC output
modules: Relay and Transistor. For relevant electrical
specification, please refer to the function specification.
2. Be careful with the connection of the common
terminals when wiring outputs. For example, when
wiring DVP12SX11R, output terminal Y0 uses one
common terminal C0, Y1 uses C1, as shown below:
C0
Y0
C1
Y1
Action indication: When the output point is active, the
corresponding indicator at the front will be on.
3. Isolated circuit: The optical coupler is used to isolate
signals between PLC internal circuits and input
modules.
Analog Input/Output Point Wiring
CH0
100K
250
-10V~+10V
V+
I+
COM
CH1
250
-20mA~+20mA
V+
I+
COM
*3
*2
AG
AG
Current input
Voltage input
Shielded*1
Shielded*1
100K
CH0
CH1
100K
100K
Note 1:
Please isolate analog input and other power
wiring.
Note 2:
If input signal is in current, please short out
between V+ and I+ terminals.
Note 3:
If the noise interference from loaded input wiring
terminal is significant, please connect a
capacitor with 0.1 ~ 0.47µF 25V for noise
filtering.
V+
I+
COM
CH0
-10V~+10V
*5
CH0
V+
I+
COM
CH1
-20mA~2 0mA
CH1
24+
24-
DC24V
DC/DC
+15V
-15V
AG
vol tage output
current output
AC drive, recorder,
scale valve...
shi elding cable *1
shieldi ng cable *4
AC drive, recorder,
scale valve...
terminal of
power module
class 3 grounding
(100 or less)
converter
Note 4:
Please isolate analog output and other power
wiring.
Note 5:
If the noise interference from loaded input wiring
terminal is significant, please connect a
capacitor with 0.1 ~ 0.47µF 25V for noise
filtering.
Note 6:
Please connect
power module terminal and
analog output module terminal to system
earth point and make system earth point be
grounded or connects to machine cover.
Warning:
DO NOT wire to the No function terminal
SA/SX/SC PLC
OPEN TYPE /
:
/
DVP DVP-SX 10 4DI+2DO+2AI+2AO SA/SX/SC
2CH 12-bit / 2CH 12-bit /
/ 2
1
2
RUN/STOP
3
2
4
I/O
5
DIN
6
I/O
7
/
8
COM1 (RS-232)
(Rx)
9
COM2 (RS-485)
(Tx)
10
COM1 (RS-232)
(Slave)
mm
11
12
13
14
DIN (35mm)
15
16
COM2 (RS-485)
(Master/Slave)
17
18
2 pin
19
20
21
3 PLC
22
DVP10SX11R/T DVP08SM11N DVP08SN11R/T DVP08SP11R/T DVP16SP11R/T
24V DC -15% ~ 20%
2A/250V AC -
5W 1W 1.5W 1.5W 2W
5M / 500V DC
ESD: 8KV Air Discharge
EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication I/O: 250V
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS: 26MHz ~ 1GHz, 10V/m
L,N PLC
/
0°C ~ 55°C 50 ~ 95% 2
-25°C ~ 70°C 5 ~ 95% D/A 0°C ~ 50°C
/ IEC61131-2, IEC68-2-6 (TEST Fc)/IEC61131-2 & IEC68-2-27 (TEST Ea)
, g
138 / 133 64 88 / 68 90 / 70 96 / 76
SINK SOURCE
-R -T
24V DC 5mA
1.5A/1 5A/COM
0.3A/1 @ 40°C
, Y0 Y1 30mA
Off On,
X0 X1 18.5V DC
X2 X3 16.5V DC
250V AC,30V DC
30V DC
On Off,
X0~X3 8V DC
75VA
90W
9W/1
Y0 Y1 0.9W
Y0 50KHz Y1 10KHz
10ms D1020 D1021
0 ~ 20ms
10 ms
Off On 20us
On Off 30us
Y0 Y1
I/O
DI
AI
DI AI DO
AO
DO AO
DVP10SX11R 4
2
2
2
DVP10SX11T
24VDC
+20%
-15%
4
2
DC24V/5 mA
Sink Source
-20 ~ 20mA
( -1,000 ~ +1,000)
-10 ~ +10V
( -2,000 ~ +2,000)
2
2
-20 ~ 20mA
( -2,000 ~ +2,000)
-10 ~ +10V
( -2,000 ~ +2,000)