Emerson 300 Power Supply User Manual


 
Chapter 4 Operator Control And Display Panel 31
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA User Manual
No. Menu Item Explanation
Communication address
This setting applies to RS485 communication and the
“one-to-multiple points” communication mode of parallel system. It is
required to set the parameter Host communication mode of COM1 in
parallel system to Multipoint to point using background software
before setting the communication address of each UPS module
Communication mode
Reserved modem function. No need to change the default setting
“RS232”
Callback times (reserved)
Phone No.1 (reserved)
Phone No.2 (reserved)
Phone No.3 (reserved)
9 Settings
Command password
Modifies password for the Command menu.
Use the Shift key (F1) to highligt Command Password, press the
Enter key (F4).
Enter each old password digit with up arrow (F2) and use right arrow
(F3) to access next field. Press the Enter key (F4) when all digits
have been entered.
Follow prompts and repeat the process for new password
Battery maintenance test
Manually initiates battery maintenance test, which will lead to the
battery being partly discharged, for rough assessment of the battery
capacity.
The Load must exceed 20% and be less than 80% of rated UPS
capacity, and the battery must have been float charging for 5 hours or
more.
Use the Shift key (F1) and up and down arrow keys (F2, F3) to
highligt the desired test. Press the Enter key (F4).
Enter each password digit with up arrow (F2) and use right arrow (F3)
to access next field. Press the Enter key (F4) when all digits have
been entered
Battery capacity test
Manually initiates battery capacity test, which will lead to the battery
being completely discharged, for accurate assessment of the battery
capacity.
The Load must exceed 20% and be less than 80% of rated UPS
capacity, and the battery must have been float charging for 5 hours or
more.
Use the Shift key (F1) and up and down arrow keys (F2, F3) to
highligt the desired test. Press the Enter key (F4).
Enter each password digit with up arrow (F2) and use right arrow (F3)
to access next field. Press the Enter key (F4) when all digits have
been entered
System test
Manually initiates the system test.
The user actives this function, after 5 seconds, a pop window will
appear to show the result of this diagnosis: Rectifier, Inverter, Monitor
OK or Fault
Stop testing
Manually stop the test, including maintenance test, capacity test and
system test
Freshening charge
Manually initiates freshening charge, when the battery is not in boost
charge state.
Use the Shift key (F1) and up and down arrow keys (F2, F3) to
highlight this item. Press the Enter key (F4).
Enter each password digit with up arrow (F2) and use right arrow (F3)
to access next field. Press the Enter key (F4) when all digits have
been entered
10 Command
*
Stop freshening charge Manually stop the freshening charge
Monitor Version
Vxxx
Rectifier Version
Vxxx
Inverter Version
Vxxx
Displays UPS firmware versions, including inverter, rectifier,
monitoring board firmware versions
11 Version
UPS model Displays UPS model information; for example, 380V-50Hz
Note*: password controlled. The default passward is “12345”, please enter Settings=>Command password to change the
password. In case the password is lost, please contact the local customer service center of Emerson