4.1 Data Arrays
The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable
the FieldServer for SBT-FSI communications, the driver independent FieldServer buffers need to be declared in the
“Data Arrays” section, the destination device addresses need to be declared in the “Client Side Nodes” section, and
the data required from the Servers needs to be mapped in the “Client Side Map Descriptors” section. Details on
how to do this can be found below.
Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.
Section Title
Data_Arrays
Column Title Function Legal Values
Data_Array_Name Provide name for Data Array
Up to 15
alphanumeric
characters
Data_Array_Format
Provide data format. E
ach Data Array can only take on one
format.
4
Int16, Uint16, Bit
Data_Array_Length
Number of Data Objects. Must be larger than the data storage
area required by the Map Descriptors for the data being placed in
this array.
1-10,000
Example
// Data Arrays
Data_Arrays
Data_Array_Name ,Data_Format ,Data_Array_Length
Event_Counts ,Uint16 ,19
Fire ,Bit ,2048
Fire_UnAck ,Bit ,2048
4
Format must be Uint16 or Int16 to see trouble codes.