Fujitsu C122-E119EN Server User Manual


 
1.3 Installation Specifications
This section lists the installation specifications of each device.
- 1.3.1 PRIMEQUEST 1800E2 installation specifications
- 1.3.2 PRIMEQUEST 1800E installation specifications
- 1.3.3 PCI_Box installation specifications
1.3.1 PRIMEQUEST 1800E2 installation specifications
TABLE 1.2 PRIMEQUEST 1800E2 installation specifications
Item Description
External
dimensions
[mm (in.)]
Width 482 (18.98)
Depth (*1) 800 (31.50)
Height 530 (20.87)
Weight [kg (lb)] (*2) 150 (330)
Air conditioning
requirements
Maximum heat output [kJ/h (BTU/h)] 14,400 (13,649)
Exhaust air
flow [m
3
/min
(ft
3
/min)] (*3)
FAN at low speed (Low) 14 (494)
FAN at normal speed (Normal) 21 (742)
FAN at high speed (High) 24 (848)
Temperature
and humidity
requirements
(*4)
Operating Temperature [°C (°F)] (*5)
Humidity [%RH] 20 to 80
Maximum wet-bulb
temperature [°C (°F)]
29 (84.2)
Non-operating (*6) Temperature [°C (°F)] 0 to 50 (32 to 122)
Humidity [%RH] 8 to 80
Maximum wet-bulb
temperature [°C (°F)]
29 (84.2)
Noise [dB] (*7) (*8) 61
Acoustic power level [B] (*8) 7.8
Allowable
vibration [m/
s
2
(gal)]
Operating (including standby state) 4.0 (400) (synthetic seismic
waves)
Non-operating (*9) 10.0 (1000) (synthetic
seismic waves)
Allowable dust concentration [mg/m
3
] 0.15
Power
requirements
Input voltage and number of phases 200 to 240 VAC ±10%
1φ
Frequency and fluctuation range 50/60 Hz +2/-4%
PRIMEQUEST 1000 Series Hardware Installation Manual
CHAPTER 1 Installation Information
6 C122-H004-07EN