Item Description
Maximum
power
consumption/
apparent
power
Operating Input voltage: 200 V 4.00 kW / 4.21 kVA
Standby Input voltage: 200 V 95 W / 126 VA
Power factor (*10) 0.95 or more
Rush current [A] (Inrush time) (*11) 20 or less
Leakage current [mA] (*12) 3.5 or less
*1 The dimensions do not include protrusions.
*2 The values are for the device with all options installed.
However, the values do not include the weight of mounted rack-mount rails (7 kg) and cables.
You can use the following formula to calculate the weight of the device based on its configuration:
Equipment weight = 86 + (11 x A) + (8 x B) + (2 x C) [kg]
- A = Number of mounted SBs (1 to 4)
- B = Number of mounted IO Units (1 or 2)
- C = Number of mounted expansion power supply units (0 to 2)
*3 If the intake air temperature is high (but within the normal temperature range), the fan enters high-speed mode
even when operation is normal.
*4 Condensation is not permitted.
*5 The temperature requirements depend on the altitude at the installation site.
- Installation at 0 to 500 m (0 to 1640 ft.) above sea level: 5 to 35°C (41 to 95.0°F)
- Installation at 500 to 1000 m (1640 to 3281 ft.) above sea level: 5 to 34°C (41 to 93.2°F)
- Installation at 1000 to 1500 m (3281 to 4921 ft.) above sea level: 5 to 33°C (41 to 91.4°F)
- Installation at 1500 to 3000 m (4921 to 9843 ft.) above sea level: 5 to 30°C (41 to 86.0°F)
The altitude specifications for the installation site include an allowable margin of error of ±100 m.
*6 "Non-operating" refers to the condition where a device has been disconnected from the power supply and stored.
*7 The actual acoustic noise level depends on the listener's location and the rack mounting conditions.
*8 The noise and acoustic power levels depend on the ambient temperature.
*9 "Non-operating" refers to the installed device in the power-off state.
*10 This is the value during operation.
*11 This value is for a single input cable.
*12 This value is for a single device.
1.3.2 PRIMEQUEST 1800E installation specifications
TABLE 1.3 PRIMEQUEST 1800E installation specifications
Item Description
External
dimensions
[mm (in.)]
Width 482 (18.98)
Depth (*1) 800 (31.50)
Height 530 (20.87)
PRIMEQUEST 1000 Series Hardware Installation Manual
CHAPTER 1 Installation Information
7 C122-H004-07EN