GE GFK0579B Scanner User Manual


 
C
137Appendix C Logicmaster 90–70, Rel. 3: Series 90–70 PLC Configuration for Remote Drops
Step 3: Configure the Remote I/O Scanner
On this screen, enter the Remote Drop ID and the I/O map to be used for the Remote
I/O Scanner.
Input Def : OFF
Out Rnable: YES
Bus Adr
29
Entering the Scanner’s Remote Drop ID
The Scanner’s Remote Drop ID is its remote drop communications ID. The range of
possible IDs is 16–254. If this is the first remote drop to be configured, the number 16
should appear in the REMOTE DROP ID: field. If other remote drops have already
been configured, a higher number appears––the software automatically increments
the ID number to avoid conflicts. If the remote drop is part of a multidrop network, it
must be configured with a unique Remote Drop ID.