GE GFK0579B Scanner User Manual


 
6
Series 90–70 Remote I/O Scanner User’s Manual – July 199294
Display I/O Modules in Remote Drop
When you enter the Configure Block screens, the Hand held–Monitor displays the
configuration of the first I/O module in the remote drop. An example is shown below.
This is a read–only function; I/O module configuration cannot be changed with the Hand–held
Monitor. Note that these displays will indicate the presence of Analog Expander
(16–channel analog), PCM, GDS, ADS, Bus Receiver (BERA), Bus Transmitter (BETA),
jumper modules and empty slots, even though none of these can be configured by the
Hand–held Monitor.
ID#143 R:0 S:2
32PT 120VAC %I
1
nxt
For each module, the display shows:
the Remote Drop ID (143 in this example)
R: the rack number. For Remote I/O Scanner version IC697BEM733A, this
must be rack 0.
S: the module’s slot number
% the module’s I/O type
the beginning I/O reference (in the example above, 1 in the third line
represents %I0001).
Pressing F4 (nxt) displays the next module. For example:
ID#143 R:0 S:3
32PT 120VAC %Q
1
nxt
In this example, the module in rack 0, slot 3 is a 32–point output board. Its beginning
output reference is %Q0001.
If a slot is not occupied, the HHM displays:
ID#143 R:0 S:4
EMPTY SLOT
nxt
Press F4 (nxt) to continue going through the module screens.