GE GFK-0787B Noise Reduction Machine User Manual


 
6
6-33GFK-0787B Chapter 6 Configuration
Analog I/O Group Configuration
Select Analog to configure any analog group. Select a triplex, duplex, or simplex analog
input group, then select the block type (6 inputs or 4 inputs/2 outputs). For example:
Note: A “simplex” input group has just one I/O block, installed on one bus, but
configured as a GMR block. It is not the same a “non-voted” block. To configure a GMR
group with just one analog block, select Simplex Analog from the menu of analog group
types as described above.
Enter a name or a description of up to 12 characters, such as
“in group 6”. This entry is for your information only. It is not used by
the GMR software.
The voted analog references start at %AI0001. The size of the voted
analog input area is determined by the number of voted analog inputs
including spares. Within this area, enter the starting %AI Input Table
reference for the block. This will be the %AI address of the voted input
data. The actual %AI references used for the “raw” input data from the
block (shown as A inputs, B inputs, C inputs in the diagram below) are
configured using the Logicmaster 90 software. The GMR configuration
software will provide a printout of the addressing required for
Logicmaster 90. The allowable reference range is 1 to 1024.
Voted Inputs
non-voted
Inputs
Input
Voting
Logic
A inputs
A
B
C
B inputs
C inputs
%AI0001
Duplicate addresses are not allowed within a GBC group. You will not
be permitted to continue until you have entered a unique address.
Enter a serial bus address from 0 to 28. Duplicate bus addresses are also
not permitted within a GBC group. However, each block in the group uses
the same serial bus address on its respective bus.
ID
Start %AI
SBA