6-48 Genius Modular Redundancy Flexible Triple Modular Redundant (TMR) System
User’s Manual – March 1995
GFK-0787B
12. On the bus configuration screen, the Bus
Controller appears at its configured Bus
Address, 31 in this example.
13. From here, you can configure the devices
on the bus, including the other bus
controllers in the group. Each bus controller
must be configured both individually and as a
device on the bus of the other bus controller(s)
on the same bus. In addition, the bus
controllers on a Global Data bus must be
configured with an appropriate Global Data
address and length.
When configuring I/O blocks, be sure to
match I/O address assignments and serial
bus addresses of GMR blocks to those
made using the GMR Configuration
Software.
Note: For input blocks in GMR groups, the I/O addresses configured on these screens are for the “raw”
input data received directly from the blocks (for the A, B, and C areas of the Table, as described in the
Programming chapter. For output blocks in GMR groups, the output addresses configured on these
screens are for the physical redundant output data (not the logical addresses used in the application
program). These addresses are produced by the GMR Configuration Software, and are listed in the
configuration printout.