5-18 Genius Modular Redundancy Flexible Triple Modular Redundant (TMR) System
User’s Manual –March 1995
GFK-0787B
PLC Fault Table Messages for GMR
The following tables lists PLC Fault Table messages for GMR.. If you need additional
help, call GE Fanuc Technical Service at 1–800–828–5747.
Code Message Meaning
100 No CPU Clock There is no PLC clock present
100 No PLC Clock There is no PLC clock present
101 Illegal state step Internal GMR error: invalid step
101 Illegal trans code Internal GMR error: invalid transition code
101 Bad trans x from wwww Internal GMR error: attempted transition to invalid step
100+
GBC ID
CFPT, 0 attempts wwww Number of attempts exhausted while trying to send a COMREQ
10009 GMRx ornge GBC g req Out of range Bus Controller (g) was requested by GMRx module
10009 GMRx bad GBC g req Unconfigured Bus Controller (g) was requested by GMRx module
10010 GMRx ornge GBC g rel Out of range Bus Controller (g) was released by the GMRx module
10010 GMRx bad GBC g rel Unconfigured Bus Controller (g) was released by the GMRx module
10011 GMRx ornge GBC g flt Out of Range Bus Controller (g) was faulted by the GMRx module
10011 GMRx bad GBC g flt Unconfigured Bus Controller (s) was faulted by the GMRx module
1 Unauthorized GMR Access Initialization module was invoked with incorrect password
10102 Incorrect GMR Version Initialization module was called with incorrect version number
10103 GMR Software Exception An invalid call number was detected
10104 Invalid GMR Pointer Initialization module was invoked with invalid pointer for diagnostics area
10109 Prog Checksum Timeout PLC didn’t calculate the program checksum within 10 seconds
10110 Invalid Bus Address Initialization detected bus addresses not equal to 29, 30, or 31
10111 Sync Not Possible Synchronization cannot be performed
10112 Output discrepancy Output discrepancy detected
10113 Miscomp, no more retries Sync detected miscompare
10114 GMR Coldstart GMR is performing coldstart
10115 GMR Warmstart GMR is performing a warmstart
10116 Cannot get all GBCs Cannot acquire all GBCs during initialization
10117 Cannot do VME Write The VME Write to 7F3h was unsuccessful
10119 Invalid Switch Case An invalid case condition was detected during a switch
10120 Failed Disable Ops The Disable Outputs command (COMREQ) failed to complete successfully
10121 Failed Enable Ops The Enable Outputs command (COMREQ) failed to complete successfully
10122 Failed Set GMR Mode The Set GMR Mode command (COMREQ) failed to complete successfully
10123 Failed DG Dgrams The Clear Datagrams Dequeue command (COMREQ) failed to complete successfully
10124 Failed Read Address The Read Bus Address command (COMREQ) failed to complete successfully
10129 Num dequeues = n N dequeue entries were dequeued at startup
10130 Program mismatch A/B PLCs A and B program mismatch, C is not online
10131 Program mismatch B/C PLCs B and C program mismatch, A is not online
10132 Program mismatch A/C PLCs A and C program mismatch, B is not online
10133 Program mismatch A/B&C PLC A program mismatch with B and C
10134 Program mismatch B/A&C PLC B program mismatch with A and C
10135 Program mismatch C/A&B PLC C program mismatch with A and B
10136 Program mismatch A/B/C All three PLCs mismatch
10137 Program changed A PLC A program changed
10138 Program changed B PLC B program changed
10139 Program changed C PLC C program changed
10140 Config mismatch A/B PLCs A&B config mismatch, C not online
10141 Config mismatch B/C PLCs B and C config mismatch, A is not online
10142 Config mismatch A/C PLCs A and C config mismatch, B is not online
10143 Config mismatch A/B&C PLC A config mismatch with B and C
10144 Config mismatch B/A&C PLC B config mismatch with A and C
10145 Config mismatch C/A&B PLC C config mismatch with A and B