5-20 Genius Modular Redundancy Flexible Triple Modular Redundant (TMR) System
User’s Manual –March 1995
GFK-0787B
Code MeaningMessage
10814 GMR cfg err no of PLCs GMR Configuration Module detected more than 3 PLCs in the config data
10815 GMR cfg err W/dog timer GMR Configuration Module detected invalid watchdog time in the config data
10817 GMR Cfg Err %R usage GMR Configuration Module detected insufficient %R registers
10818 GMR cfg err %AI Usage GMR Configuration Module detected insufficient PLC Analog Inputs
10819 GMR cfg err comreq %R GMR Configuration Module detected invalid positioning of the comreq status %R
area
10820 GMR cfg err Tx global GMR Configuration Module detected invalid positioning of the Tx global comms %R
area
10821 GMR cfg err Rx global GMR Configuration Module detected invalid positioning of the Rx global comms %R
area
10822 GMR cfg err I/O > max GMR Configuration Module detected that the maximum I/O points has been exceed-
ed
10823 GMR cfg err voted DIN GMR Configuration Module detected that the maximum number of voted digital
inputs has been exceeded
10824 GMR cfg err voted AIN GMR Configuration Module detected that the maximum number of voted analog
inputs is exceeded
10825 GMR cfg err redund O/P GMR Configuration Module detected that the maximum number of redundant out-
puts is exceeded
10826 GMR cfg err alpha rack GMR Configuration Module detected that alpha inter-PLC GBC is in an invalid rack
10827 GMR cfg err alpha slot GMR Configuration Module detected that alpha inter-PLC is in an invalid slot
10828 GMR cfg err beta rack GMR Configuration Module detected that beta inter-PLC is in an invalid rack
10829 GMR cfg err beta slot GMR Configuration Module detected that beta inter-PLC is in an invalid slot
10830 GMR cfg err %M sync GMR Configuration Module detected invalid positioning of the %M sync area
10831 GMR cfg err %R sync GMR Configuration Module detected invalid positioning of the %R sync area
10832 GMR cfg err %R temp GMR Configuration Module detected invalid positioning of the %R temp %M sync
area
10833 GMR cfg err %R A/T int GMR Configuration Module detected invalid positioning of the %R autotest interval
pointer
10834 GMR cfg err ssu flt act GMR Configuration Module detected invalid system startup fault action
10835 GMR cfg err syc flt act GMR Configuration Module detected invalid startup sync fault action
10837 GMR cfg err no of GBCs GMR Configuration Module detected invalid number of GBCs
10840 GMR version MM.mmE GMR software version number
10841 Cfg util ver MM.mmE GMR config utility version number
10842 GMR config crc 0xXXXX Config utility CRC value
10843 XXXXXXXXXXXXXXXXXXXX First 20 characters of config description
10844 XXXXXXXXXXXXXXXXXXXX Remaining characters of description
10850 Invalid Dig I/P data Invalid data detected in voted digital input record
10851 Invalid NV Dig I/P data Invalid data detected in nonvoted digital input record
10852 Invalid Ana I/P data Invalid data detected in voted analog input record
10853 Invalid NV Ana I/P data Invalid data detected in nonvoted analog input record
10860 GMR cfg err %R Write %R register external device write access range is invalid
10861 GMR cfg err %AI Write %AI register external device write access range is invalid
10862 GMR cfg err %AQ Write %AQ register external device write access range is invalid
10863 GMR cfg err %I Write %I register external device write access range is invalid
10864 GMR cfg err %Q Write %Q register external device write access range is invalid
10865 GMR cfg err %T Write %T register external device write access range is invalid
10866 GMR cfg err %M Write %M register external device write access range is invalid
10867 GMR cfg err %G Write %G register external device write access range is invalid
10870 Shutdown in hh mm ss System simplex shutdown in hh hours, mm minutes and ss seconds
10871 Shutdown Cancelled System simplex shutdown cancelled
10872 System Shutdown System has shut down
10894 Config changed r.s.b.d. The block-level configuration was changed by the specified device.
10898 GMR Fault Handler Error Fault handler received a fault for an invalid discrete block
10899 GMR Fault Handler Error Fault handler received a fault for an invalid analod block
10902 User_IF–GMR version Module version number does not match the GMR system version number