Generac Power Systems 5465 Switch User Manual


 
ENVIRONMENTAL SPECIFICATIONS
Operating Temperature .......................................................................................................................................................................... -25 º C to 60 º C
Humidity ............................................................................................................................................................................... 0 to 95% Non-Condensing
Power Supply ..........................................................................................................................................................................................+12 or +24 VDC
Power Usage ............................................................................................................................................................................................ 6 Watts typical
Power Supply .......................................................................................................................................................................................Generator Battery
Communication Line ..........................................................................................................................RS485 fully isolated twisted pair cable with shield
Maximum Cable Length .................................................................................................................................................................................... 4000 feet
Relay Output .............................................................................One NO contact (Engergized when annunciator is powered and no faults are present)
Relay Contact Rating .............................................................................................................................................................................. 30 VDC, 1 amp
STANDBY GENERATOR ACCESSORIES
21 Light Remote Annunciator
Liquid-Cooled Generator Sets
Model 5465
Model 5466
Model 5464
The Remote Annunciator Panel provides remote monitoring and
annunciation of up to 18 generator parameters using LED’s located on
the annunciator keypad. It also provides two system level warnings which
are System Ready and Communications OK.
The Relay panel has up to 8 selectable functions on form A relays,
and multiple relay panels can be connected for all 18 generator
parameters.
The specific faults can be selected using either the DIP switches located
on the annunciator circuit board or through a computer via the RS232
connection on the circuit board. All relays are energized on power up and
open during a fault condition.
Communication is via a RS485 serial data link and power is supplied by
the generator battery (+12 VDC or +24 VDC)
Note: These units are only compatible with the H-series generator
controller (70-150 kW)
DESCRIPTION