Liebert Corporation • 1050 Dearborn Drive • PO Box 29186 • Columbus, OH 43229
Phone 607-724-2484 • Fax 607-722-8713 • US & Canada 800-288-6169
EMAIL: info@control-concepts.com • Web Site: www.Liebert.com 82245 Rev 0
UL 1449 second edition clamping data
Voltage L-N L-G L-L N-G
100-120V 400 400 800 400
208V 800 800
230-277V 800 800 1500 700
347V 1200 1000 2000 1000
400-480V 1500 1500
600V 2000 2000
Liebert Active Tracking Filter System
Technical Specification
Operating Voltage Range.........................................+/-15%
Fault Current Rating (AIC)........................................200 kAIC
Operating Frequency Range....................................47 – 63 Hz
50 EMI/RFI Attenuation:
Normal Mode..............................................10 kHz-500MHz 60 dB
Common Mode...........................................10 kHz-500MHz 50 dB
Response Time .........................................................<0.5 ns
Operating Humidity................................................... 0% to 95%
Status Indication.......................................................LEDs, Dry Contacts, Audible Alarm,
Surge Counter
Certifications.............................................................UL 1449 & 1283, CSA
Enclosure ..................................................................NEMA 12 standard
Warranty ....................................................................10-Years Parts / 5-Years Labor
Optional Equipment..................................................Dual Surge Counter,
Remote Monitor Panel
Dimensional data in inches and shipping weight in pounds
Model/Configuration Dimensions in inches Wt
A B C D E F Lbs
30A Single Phase 20.0 16.0 9.0 21.25 10.0 .44 35
30A Split or Three Phase 24.0 20.0 9.0 25.25 14.0 .44 60
60A Single Phase 20.0 16.0 9.0 21.25 10.0 .44 35
60A Split or Three Phase 24.0 20.0 9.0 25.25 14.0 .44 60
100A Single Phase 24.0 20.0 9.0 25.25 14.0 .44 60
100A Split or Three Phase 30.0 24.0 9.0 31.25 18.0 .44 80
225A Single Phase 24.0 20.0 9.0 25.25 14.0 .44 60
225A Split or Three Phase 30.0 24.0 9.0 31.25 18.0 .44 80
400A Split or Three Phase 48.0 36.0 12.0 49.25 30.0 .44 300
800A Split or Three Phase 60.0 48.0 12.0 - - - 530
1200A Split or Three Phase 60.0 48.0 20.0 - - - 750
2000A Split or Three Phase 60.0 48.0 20.0 - - - 950
4000A Split or Three Phase 60.0 48.0 20.0 - - - 1300
Nominal
Voltage Codes
120 120V
208 208V
220 220V
230 230V
240 240V
277 277V
480 480V
600 600V
Source configuration
N 1 Phase L-N 2w + gnd
L 1 Phase L-L 2w + gnd
S Split Phase 3w + gnd
Y 3 Phase Wye 4w + gnd
D 3 Phase Delta 3w + gnd
H 3 Phase Delta Hi-leg 4w+ gnd
F__ __ __ __ __ __ __ __ - __ __
Option Code
01
LED, Form C
Contacts
03
LED, Alarm, Dual
Counters, Form C
Contacts
06
LED, Alarm, Counter,
Form C Contacts
E
xample Part Number: F277Y800-03 = 277/480V, 3-Phase Wye, All Mode, 800 Amp Current Rating
LED’s, Alarm & Dual Counters, Form C Contacts
Current
Code
Current
Rating
Surge Current Capability
Per Phase
30 30A 100kA
60 60A 100kA
100 100A 150kA
225 225A 150kA
400 400A 150kA
800 800A 300kA*
1200 1200A 300kA*
2000 2000A 300kA*
4000 4000A 300kA
* 200kA is available,
add –200 to part number.
Job Name
_
___________________________
Model# ______________________________
Date ________________________________
Qty _________________________________
Quote# ______________________________
Life Cycle Surge Testing
10kA, 20kV, IEEE Cat. C3
Unit Per Mode (L-N/L-G/N-G) Per Phase
100 kA 12,000/12,000/12,000 24,000
150 kA 12,000/24,000/24,000 36,000
200 kA 24,000/24,000/24,000 48,000
300 kA 24,000/48,000/48,000 72,000