Liebert Intellislot
®
Web/485 Card
With Adapter
Quick Start Guide
INSTALL
• Locate the adapter mounting location within your Liebert equipment.
• Secure the card with the supplied screws.
• Connect the equipment's communication cable to the TB1 terminal
block or P1 on the card (See equipment user manual for details).
• Connect an Ethernet cable to RJ45.
• Connect a Modbus (RS-485) cable to the TB2 terminal block.
• Connect an input power supply cable to Pins 1 & 2 on the TB3 terminal
block; Pin 1 is at the far left, and Pin 2 is the middle pin.
DHCP: The card ships with DHCP service enabled. The MAC address is
printed on a sticker affixed to the top of the card.
OR
Static IP: To assign a static IP address, use the Service Terminal to con-
figure the card. Proceed to Steps 2 & 3.
CONNECT THE CABLE
• Locate the blue serial configuration cable (null modem) that shipped
with the card.
• Connect the configuration cable to the DB-9 port on the card and to a
COM port on your PC.
CONFIGURE THE CARD
• Use terminal emulation software, such as
HyperTerminal
™
, to open a direct connec-
tion to the card.
•Press Enter for the Main Menu.
• Select option 2 and follow the instructions
to enter an IP ADDRESS,
NETMASK and GATEWAY.
•Press Esc to return to the Main Menu.
• Enter X and press Enter to exit HyperTerminal and save your
changes.
TB2
(P1: +)
(P2: -);
P1 is at the
right side of
terminal block.
Network Port
for NMS and
Web Access
TB3
(P1: +)
(P2: -)
(P3: NC)
P1 is on
left end of
terminal
block.
DB-9
Port
MAC Address
P1
TB1 (P1: +; P2: -); P1 is at the
right side of terminal block.
Emulation Software
Configuration
Baud Rate: 9600
Data Bits: 8
Parity: None
Stop Bits: 1
Flow Control: None