5.2 Positioning the units
After positioning, the feet on the CoolTherm are to be set such that the cabinet is vertical. When
positioned the doors must close easily.
The feet are adjusted using a spanner (spanner width 65mm). Watch the length of the thread.
As an option it is possible to connect the cabinets together. There for remove the plugs from the
side panels and connect with hex screw, item no. 4000 1411.
Distance
feets
B1
(mm)
T1
(mm)
W700 D1200
600 1114
W800 D1200
700 1114
W800 D1300
700 1214
Adjustable Feet
Remove recirculation air duct transport lock
After positioning remove the transport lock screws at the sides of the recirculation air duct.
The recirculation air duct can be pulled out to remove items which possibly had felt into the head
exchanger tray.