Lightolier LUPS Series Power Supply User Manual


 
LUPS Series Uninterruptible Power Supplies LUPS
Page 1 of 2 550 - 1,500 VA Sine Wave UPS System
J
ob Inf
ormation Type:
J
ob Name:
Cat. No.:
Lamp(s):
Notes:
Lightolier a Genlyte Company
www
.lightolier
.com
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
W
e r
eser
ve the right to change details of design, materials and finish.
© 2006 Genlyte Gr
oup LLC (Lightolier Division) •
C0406
Overall Characteristics
83% throughput efficiency
Single conversion UPS, No transfer time
Operating temperature range of 32°F (0°C) to 104°F (40°C); 65°F (19°C) to
85°F (29°C) maximum for batteries
Standard 90 minutes of operating time
Full-time, isolating transformer
Variable Range Regulator allows wider range of acceptable input voltage
variation
ANSI/IEEE C62.41 category A & B surge voltage withstand capability
Housing
Free standing, NEMA 1 enclosure with locking doors
Acid resistant powder coat finish
Multiple conduit entries
Standard Metering/Controls
AC input and output voltage
AC input br
eaker
AC output breaker
Battery disconnect device
Automatic battery monitor with alarm
LED indicating lamps for system on, system on battery, low battery warning
Battery
Maintenance fr
ee, sealed lead calcium battery has an estimated service life of
10 years, and operating temperature range of 65°F (19°C) to 85°F (30°C)*.
* Increases or decreases in temperature will affect battery performance. Optimum battery performance
r
ealized at 77
°F (25°C). Batteries are rated at 100% capacity at 77°F (25°C).
Electronics
Input
Input power factor self-correcting to > 0.95
Frequency 60.0 ±2.5 Hz
Input voltage tolerance +10% to -15%
Input harmonics < 8% THD
Output
Solid-state PWM inverter with sine wave output
Output voltage regulation ±3% of nominal at full load
Output frequency 60 Hz ±0.2%
Load power factor capability is 0.6 lagging to unity
Overload rating: 125% for 10 minutes
Efficiency: 82% to 86%
Charger
Low voltage disconnect (L
VD)
3 amp, 2-stage
Rechar
ge time: UL 924 compliant
Options
FSU = Start-up Service
EXT = Extended Warranty (with FSU only)
How to Specify:
3
1.0”
7
8.7 cm
3
9.0”
99.1 cm
5
50 VA 1000 VA 1500 VA
Cabinet &
223 lbs. 223 lbs. 262 lbs.
E
lectronics
(
101 kg) (101 kg) (119 kg)
S
ealed Lead
Calcium Battery
1
0 Minute 44 lbs. 59 lbs. 88 lbs.
B
ackup (19.9 kg) (26.8 kg) (39.9 kg)
20 Minute 54 lbs. 88 lbs. 108 lbs.
B
ackup (24.5 kg) (39.9 kg) (49.0 kg)
90 Minute 121 lbs. 203 lbs. 288 lbs.
Backup (55 kg) (92 kg) (131 kg)
LUPS
Series VA Rating Voltage Output Circuit
C
onfiguration Breakers
L
UPS
=
LUPS Uninterr
uptible 550 = 550 VA Input Output OCB1 = (550 VA)
Power Supply for 1000 = 1,000 VA A = 120 120 OCB3 = (1000, 1500 VA)
Emergency Lighting 1500 = 1,500 VA B = 277 277
A
pplications
LUPSX = 10 Minute Backup
LUPSY = 20 Minute Backup
1
6.6”
4
2.2 cm
Operates incandescent, electronic ballast loads and HID lighting loads as well as critical loads requiring conditioned emergency power.