Mitsubishi Electronics OC376 Noise Reduction Machine User Manual


 
25
• Name, Symbol and the Maximum Remote controller Units for Connection
Name
Outdoor unit
Indoor unit
Symbol
OC
IC
RC
Maximum units for connection
Permissible Lengths Prohibited items
Longest transmission cable length
(1.25 mm
2
)
L
1 + L2, L2 + L3, L3 + L1 [ 200m
Remote controller cable length
1. If 0.5 to 1.25 mm
2
R1, R2 [10m
2. If the length exceeds 10 meters,
the exceeding section should
be 1.25 mm
2
and that section
should be a value within the
total extension length of the
transmission cable and
maximum transmission cable
length. (L
3)
Same as above
Same as above
• Use the indoor unit(IC)
address plus 150 as the
sub remote controller
address. In this case, it
should be 152.
• 3 or more remote con-
troller (RC) cannot be
connected to 1 indoor
unit.
• The remote controller
address is the indoor
unit main address plus
100. In this case, it
should be 101.
M1M2
TB5
S12
TB15
01
102
IC(Main)
AB
M1M2
TB3
SAB
TB7
51
OC
S
M1M2
TB5
S12
2
TB15
02
IC(Sub)
RC
M1M2
TB5
S12
TB15
01
101
RC
(Main)
151
IC
M1M2
TB3
SAB
TB7
51
OC
S
M1M2
TB5
S12
TB15
02
IC
RC
(Sub)
102
RC
(Main)
103
RC
(Sub)
104
RC
AB AB AB AB AB
1 OC unit can be connected to 1-8 IC units (P100 : 1-6 IC units)
Maximum 2 RC for 1 indoor unit, Maximum 16 RC for 1 OC
M-NET remote
controller
M1M2
TB5
S12
TB15
01
101
IC
AB
M1M2
TB3
SAB
TB7
51
OC
S
M1M2
TB5
S12
TB15
02
IC
RC
TB15
AB
MA
• M-NET remote controller(RC) and MA remote controller(MA) cannot be used together.
• Do not connect anything with TB15 of indoor unit(IC).