OPERATING PROCEDURE
PHOTOS & ILLUSTRATIONS
11. Removing the heat exchanger
(1) Remove the drain pan. (See Photo 6)
(2) Remove the 3 screws of the piping cover, and pull out
piping cover.
(3) Remove the 2 screws of coil plate.
(4) Remove the 2 screws of the coil.
(5) Remove the screw of the coil support.
(6) Pull out the heat exchanger.
Photo 10
Linear expansion
valve
Heat exchanger
fixing screw
Coil support
Heat exchanger