Control modes
Control details
3-1. Drain pump control
•Always drain pump ON during the COOL and DRY mode operation.
(Regardless of the thermo ON/OFF)
•When the operation mode has changed from the COOL or DRY to the others
(including Stop), OFF the control after the drain pump ON for 3 minutes.
Float switch control
• Float switch control judges whether the sensor is in the air or in the water by
turning the float switch ON/OFF.
In the water: Detected that the float switch is ON for 15 seconds.
In the air : Detected that the float switch is OFF for 15 seconds.
(1) Initial setting: Start at COOL mode and horizontal vane.
(2) Vane position:
Horizontal Downward A Downward B Downward CDownward DSwingAuto
(3) Restriction of the downward vane setting
When setting the downward vane A, B, C or D in [Med1], [Med2] or [Low] of the
fan speed notch, the vane changes to horizontal position after 1 hour have passed.
4. Vane
(up/down vane change)
3. Drain pump
Remarks
· "ONLY 1 Hr"
appears on the
wired remote
controller.
ON
OFF
15sec. 15sec. 15sec. 1min.30sec. 1min.30sec.
From the preceding page.
Float SW
In the water In the air In the water Error
postponement
Drain pump
abnormal