Murphy WD300 Series Switch User Manual


 
WD-03061B page 1 of 2
Description
WD300 Series
The universally applicable WD300 Series
panels are the ideal control solution for a
wide variety of diesel engines without shut-
down solenoid in the injection pump.
The standard WD300 Series panel includes
basic engine protection for low oil pressure
and high coolant temperature. It also includes
Murphy’s SV Series solenoid fuel shut-off
valve, (see bulletin SV-99026B).
WD300LV Models
For engines that have the fuel shut-off sole-
noid built into the injection pump. This model
also applicable to battery ignition engines.
Panel Kits Include:
Low Lube Oil Pressure Swichgage
instrument.
High Coolant/ Temperature Swichgage
instrument.
117PH Magnetic Switch.
SV Series Solenoid Fuel Shutoff Valve.
PB128S Emergency Stop Push Button.
Specifications
Low Lube Oil Pressure SWICHGAGE
®
:
0-100 psi (0-689 kPa) [0-6.89 bar]
1/8 NPT process connection
High Coolant SWICHGAGE
®
:
130-250°F (54-121°C)
48 in. (1.2 m) capillary
1/2 NPT process connection
117PH Magnetic Switch
SV Series Solenoid Fuel Shutoff Valve:
12 or 24 volt (specify)
Shipping Weight: 8 lbs. 8 ozs. (3.9 kgs.)
Shipping Dimensions:
8.5 x 5.25 x 5.5 in. (216 x 133 x 140 mm).
Warranty
A limited warranty on materials and workmanship is
given with this FW Murphy product. A copy of the
warranty may be viewed or printed by going to
www.fwmurphy.com/support/warranty.htm
WD-03061B
Revised 04-06
Catalog Section 30
Swichgage
®
Shutdown Panels with
Open Back for Diesel Engines
WD300 Series
Universal Design Ideal for Diesel Engines
Without Fuel Solenoid Built Into the
Injection Pump
Swichgage Instruments for Low Oil
Pressure, High Coolant Temperature
Includes Fuel Solenoid Shutdown Valve
WD300-LV
3-5/8 in. (92 mm)
5-1/8 in. (130 mm)
3-13/16 in. (97 mm)
3-1/16 in. (78 mm)
6-3/4 in. (171 mm)
6-1/8 in. (156 mm)
20P100
Oil Pressure
Swichgage
®
20T250-4-1/2
Temperature
Swichgage
®
117PH Magnetic Switch
PB128S Emergency
Stop Push Button
1/2-14 NPT
Adapter Nut
shipped loose
Dimensions (all Models)
NOTE: This is an standard schematic. If non-standard components
are specified, this schematic may not exactly reflect your panel.