Perle Systems 5500161-40 Server User Manual


 
269
Channels
Temperature
Temperature input channels monitor RTD or thermocouple temperature sensors inputs for the most
common ranges. You can also configure severity alarms that can send an email, a syslog message,
and/or an SNMP trap when an alarm is triggered or cleared; See
Alarm Settings on page 271 for
more information about the alarms.
RTD ranges are:
z Pt100 a=385 -50 to 150C z Pt100 a=392 -50 to 150C z Pt1000 a=385 -40 to 160C
z Pt100 a=385 0 to 100C z Pt100 a=392 0 to 100C z NiFe604 a=518 -80 to 100C
z Pt100 a=385 0 to 200C z Pt100 a=392 0 to 200C z NiFe604 a=518 0 to 100C
z Pt100 a=385 0 to 400C z Pt100 a=392 0 to 400C
z Pt100 a=385 -200 to 200C z Pt100 a=392 -200 to 200C
Note:
IEC RTD 100 ohms.=0.00385
JIS RTD 100 ohms.=0.00392
Thermocouple ranges are:
z B 500 to 1800C z K 0 to 1370C z T -100 to 400C
z E 0 to 1000C z R 500 to 1750C
z J 0 to 760C z S 500 to 1750C
In the following example, a Temperature I/O IOLAN is used to monitor industrial freezer temperature
sensors, with an alarm set to send a syslog message if the temperature rises above 31
o
C.
IOLAN
perle
Monitoring
Application
Network
Industrial
Freezers
Temperature I/O
T4