Toshiba 4200FA XT Power Supply User Manual


 
T42F3F150FAMXN
One-Line Drawing
4200FA XT UPS, 15 kVA Capacity
Isolated Redundant System, Shown with
3-Breaker External Bypass Switch
JE
DATE 08/15/05
AC Input
208/120V
3Ph/4W
60Hz
TOSHIBA
INTERNATIONAL CORPORATION
Houston Texas, USA
THIS MATERIAL IS THE EXCLUSIVE PROPERTY OF
TOSHIBA INTERNATIONAL CORPORTION AND SHALL NOT
BE REPRODUCED, USED, OR DISCLOSED TO OTHERS
UNLESS PRIOR WRITTEN AUTHORIZATION IS OBTAINED.
TITLE
DRAWING NO. REV.
NOTES
DRAWN BY
A B C D E F G H I J
1
2
3
4
5
6
7
8
9
10
1
2
3
4
5
6
7
8
9
10
1.3
Battery Cabinet(s) or Rack(s) with DC breaker
+
-
15 kVA UPS #2 Cabinet
Battery Cabinet(s) or Rack(s) with DC breaker
+
-
15 kVA UPS #1 Cabinet
Converter
DC Chopper/
Charger
HF Noise
Filter
HF Noise
Filter
Fuse
Inverter
MCCB
Contactor Fuse Contactor
Static Switch Bypass
Maintenance Bypass
SYNC
Make-Before-Break
Contactor
Fuse
1) This drawing is for illustration purposes only and is subject to change without notice. TIC
is not responsible for any errors or omissions.
Converter
DC Chopper/
Charger
HF Noise
Filter
HF Noise
Filter
Fuse
Inverter
MCCB
Contactor Fuse Contactor
Static Switch Bypass
Maintenance Bypass
SYNC
Make-Before-Break
Fuse
AC Input
208/120V
3Ph/4W
60Hz
ST
72B
ST
72B
DATE 08/15/05
JIS
Approved by
SW2
SW3
3-Breaker Maintenance Bypass Switch
SW1
SW2
SW3
3-Breaker Maintenance Bypass Switch
SW1
Contactor
AC Input
208/120V
3Ph/4W
60Hz
AC Output
208V,
3Ph/4W,
60Hz
15kVA
.8 PF