Toshiba H9 Network Card User Manual


 
180 H9 ASD Installation and Operation Manual
Preset Speed 1 Operation Mode
Program Pattern Run Operation Mode
This parameter is enabled at F560 and is used to set the speed, torque, and
direction of Preset Speed 1.
This screen is comprised of 4 fields that are labeled as follows: Direction, Acc/
Dec Group, V/f Group, and Torque Limit Group. Scroll to the field of
interest and press the scroll knob (Enter). Using the scroll knob, set the value
and press the scroll knob (Enter).
Parameters F562F575 are used to set the functions listed here for Preset
Speeds 215.
When using communications write the appropriate word to location F561 as
indicated below.
Settings:
0 — Forward Run
1 — Reverse Run
2 — Accel/Decel Switching 1
4 — Accel/Decel Switching 2
8 — V/f Switching Signal 1
16 — V/f Switching Signal 2
32 — Torque Limit Switching Signal 1
64 — Torque Limit Switching Signal 2
Direct Access Number — F561
Parameter Type — Selection List
Factory Default — Forward Run
Changeable During Run — No
Preset Speed 2 Operation Mode
Program Pattern Run Operation Mode
Same as Preset Speed 1 Operation Mode (see F561).
Direct Access Number — F562
Parameter Type — Selection List
Factory Default — Forward Run
Changeable During Run — No
Preset Speed 3 Operation Mode
Program Pattern Run Operation Mode
Same as Preset Speed 1 Operation Mode (see F561).
Direct Access Number — F563
Parameter Type — Selection List
Factory Default — Forward Run
Changeable During Run — No
F/R
V/f Switch
Torque Limit
Switch 2
A/D Switch
1
24816
3264
0
11
01
1
0
Writing the following data to location F561 via communications results in:
Forward Run, A/D SW 2, V/f SW 3, Torque Lim SW 4.
{
{
{
{
0=F
1=R
00=A/D 1
01=A/D 2
10=A/D 3
11=A/D 4
00=V/f 1
01=V/f 2
10=V/f 3
11=V/f 4
00=T-Lim 1
01=T-Lim 2
10=T-Lim 3
11=T-Lim 4
F561 F563