Specifications and Characteristics
A–8 TM-XDOP-01XN
Typical Programming Resolution
Typical Measurement Resolution
Programming Accuracy
1
Readback Accuracy
Front Panel or Remote Digital Interface
Vo l t a g e
Current
Power
Over Voltage Protection
0.002% of Vmax
0.002% of Imax
0.05% of Pmax
0.002% of Vmax
Remote Analog Programming Interface
Voltage
Current
0.002% of Vmax
0.002% of Imax
Front Panel or Remote Digital Interface
Voltage
Current
Power
0.002% of Vmax
0.002% of Imax
0.05% of Pmax
Remote Analog Programming Interface
Voltage
Current
0.002% of Vmax
0.002% of Imax
1. Accuracy specifications apply for settings in range of 1% to 100% of rated output
Front Panel or Remote Digital Interface
Voltage Programming
Current Programming
Power Programming
Over voltage
Programming
0.1% of Vmax
0.5% of Imax
0.5% of Pmax
0.1% of Vmax
Remote Analog Programming Interface
Voltage Programming
Current Programming
0.2% of Vmax
0.5% of Imax
Front Panel or Remote Digital Interface
Voltage Readback
Current Readback
Power Readback
0.15% of Vmax
0.5% of Imax
0.5% of Pmax
Remote Analog Programming Interface
Voltage Readback
Current Readback
0.3% of Vmax
0.5% of Imax
TM-XDOP-01XN.book Page 8 Monday, July 17, 2006 11:19 AM