Commissioning
4.5 Parameter menu
4.5.1 Basic Setup Parameters
Code Possible Settings
IMPORTANT
No. Name Default Selection
Start Control
Source
0 0 Local Keypad Use RUN button on front of drive to start
1 Terminal Strip Use start/stop circuit wired into the
terminal strip. See Section 3
.2.3
2 Remote Keypad Only Use RUN button on optional Remote
Keypad to start
3 Network Only • Start command must come from
network (Modbus, CANopen, etc)
• Requires optional communication
module (refer to the network module
documentation).
• Must also set one of the TB-
13
inputs to 9 (Network Enable); see
P121...P123
4 Terminal Strip or Local
Keypad
Allows start control to be switched
between terminal strip and local
keypad using one of the TB-13
inputs.
See note below.
5 Terminal Strip or Remote
Keypad
Allows start control to be switched
between terminal strip and optional
remote keypad using one of the TB-13
inputs. See note below.
WARNING!
P100 = 0 disables TB-1 as a STOP input! STOP circuitry may be disabled
if parameters are reset back to defaults (see P199)
Note
• P100 = 4, 5: To switch between control sources, one of the TB-13
inputs (P121...P123) must be set to 08 (Control Select);
TB-13x OPEN (or not configured): Terminal strip control
TB-13x CLOSED: Local (P100 = 4) or Remote (P100 = 5) keypad
• P100 = 0, 1, 4: Network can take control if P121...P123 = 9 and the
corresponding TB-13x input is CLOSED.
• The STOP button on the front of the drive is always active except in
JOG mode.
•
An fault will occur if the Assertion Level switch (ALsw)
position does not match the P120 setting and P100 is set to a
value other than 0.
Standard
Reference
Source
0 0 Keypad (Local or Remote) Selects the default speed or torque
reference when no Auto Reference is
selected using the TB-13 inputs
1 0-10 VDC
2 4-20 mA
3 Preset #1
4 Preset #2
5 Preset #3
6 Network