ADC 25-Pair Category 5e Riser Cable Network Router User Manual


 
7 / 0 7 1 0 4 7 5 2 A E
25-Pair Category 5e Riser Cable
3
w w w . a d c . c o m + 1 - 9 5 2 - 9 3 8 - 8 0 8 0 1 - 8 0 0 - 3 6 6 - 3 8 9 1
TrueNet
®
25-Pair Category 5e Riser Cable
FREQ
MHZ
Fitted
Impedance
Ohms
Insertion Loss
dB/100m
Pair-Pair NEXT
dB/100m
PSNEXT
dB/100m
Spec Max Spec Min Spec Min Spec
1 100 +/- 15 2.0 2.0 71.7 65.3 69.6 62.3
4 100 +/- 15 4.0 4.1 64.1 56.3 60.8 53.3
8 100 +/- 15 5.6 5.8 57.9 51.8 56.3 48.8
10 100 +/- 15 6.3 6.5 57.2 50.3 55.2 47.3
16 100 +/- 15 8.1 8.2 54.2 47.2 51.7 44.2
20 100 +/- 15 9.2 9.3 53.1 45.8 50.0 42.8
25 100 +/- 15 10.2 10.4 48.5 44.3 46.8 41.3
31.25 100 +/- 15 11.5 11.7 50.9 42.9 48.0 39.9
62.5 100 +/- 15 16.5 17.0 46.6 38.4 44.0 35.4
100 100 +/- 15 21.3 22.0 42.5 35.3 39.9 32.3
FREQ
MHZ
Return Loss
dB/100m
Pair-Pair ELFEXT
dB/100m
PSELFEXT
dB/100m
Max Spec Min Spec Min Spec
1 26.6 20.0 67.3 63.8 65.8 60.8
4 27.1 23.0 55.8 51.8 54.2 48.8
8 28.5 24.5 49.9 45.7 48.3 42.7
10 29.8 25.0 47.8 43.8 46.3 40.8
16 29.5 25.0 43.9 39.7 42.3 36.7
20 30.4 25.0 41.9 37.8 40.3 34.8
25 31.2 24.3 40.1 35.8 38.5 32.8
31.25 30.7 23.6 38.1 33.9 36.5 30.9
62.5 26.7 21.5 32.5 27.9 30.8 24.9
100 24.6 20.1 29.0 23.8 27.3 20.8
Description Catalog Number
1000 foot reel, 132 lbs (195 kg), Gray
5ETR-2524GY02
O rd e r in g I nf o r ma t io n
NOTE: The above listed discrete frequency electrical performance values are provided for engineering information
only. Actual compliance testing is based on swept frequency measurements. The spec values are based on TIA/EIA-
568-B.2 specification.