15
Connection Non-heating appliance
connectors
Current Crest Ratio 3:1
Overload behaviour up to 105 % ± 5 % continuous;
in battery mode > 105 % ± 5 % – < 150 % ± 5 %
for 25 s;
150 % ± 5 % for 200 ms
Overload behaviour up to 105 % ± 5 % continuous;
with existing mains > 105 % ± 5 % – < 150 % ± 5 %
for 30 s;
150 % ± 5 % for 300 ms
Then automatic inverter to
Bypass in < 4 ms (switches
back when overload damps =
Load < 90%)
Short circuit behaviour 3 x I
N
for 140 ms
Battery
Autonomy time (full load with internal battery)
PROTECT C. 1000 6 min
PROTECT C. 2000 10 min
PROTECT C. 3000 5 min
Autonomy time with external optional battery expansions
(only for PROTECT C. – models):
Coupled
Autonomy time (full load)
battery modules
C.1000 C. 2000 C. 3000
1 38 min 55 min 30 min
2 76 min 106 min 60 min
Rated direct voltage (intermediate circuit)
PROTECT C. 1000 (S) 36 V
PROTECT C. 2000 (S) 96 V
PROTECT C. 3000 (S) 96 V