16
5.1 Specifications
MODELL
PROTECT A. 1000 PROTECT A. 1400
Type
1000 VA / 600 W 1400 VA / 840 W
Input voltage
220 Vac / 230 Vac / 240 Vac
Input voltage range
without battery mode
170 – 280 Vac
UPS-input
Frequency (auto
selection)
50 / 60 Hz ± 5 Hz
Rated output voltage
/AVR-technology
220 Vac / 230 Vac / 240 Vac
Rated output voltage
in battery mode
±10%
Frequency in battery
mode
50 / 60 Hz ± 1 Hz
Transfer time at mains
outage
2 – 6 ms (typical)
UPS-output
Output Waveform
Modified sinewave
Type
12 V / 7 Ah x 2 12 V / 9 Ah x 2
Autonomy time
(full Load)
3 min
Battery
Recharge time (to
90% of rated capacity)
8 h
AC mode
Green LED lighting
LED bar graph (LED 2 to 5) indicates the load capacity
Backup mode
Green LED flashing
LED bar graph (LED 2 to 5) indicates the battery capacity
Indicator
Fault
Red LED lighting
Backup mode
Sounding every 10 seconds
Low battery
Sounding every second
Overload
Sounding every 0.5 second
Battery replacement
Sounding every 2 seconds
Acoustic alarm
Fault USP
Continuously sounding
Protection
Discharge, overcharge, and overload protection
Size
W x H x D (mm)
140 x 180 x 370
Weight (kg)
14 kg 14,5 kg
Operating temperature
range
0° - 40°C
Relative humidity: 0 – 90 % (non-condensing)
General data
Audible noise
(1 m distance)
< 45 dB (A)
Interfaces
USB and RS232 for status and measurement levels
Communication
Shutdown-Software
(on CD)
Included for all typical operating systems
(e.g. Windows, Linux, Mac)