5.1 Specifications
MODEL
PROTECT A. 500 PROTECT A. 700
Type power
500 VA / 300 W 700 VA / 420 W
Input voltage
220 Vac / 230 Vac / 240 Vac
Input voltage range
without battery mode
150 – 280 Vac
UPS-input
Frequency (auto
selection)
50 / 60 Hz ± 5 Hz
Rated output voltage
/AVR-technology
220 Vac / 230 Vac / 240 Vac
Rated output voltage
in battery mode
±10%
Frequency in battery
mode
50 / 60 Hz ± 1 Hz
Transfer time at mains
outage
2 – 6 ms (typical)
UPS-output
Output Waveform
Modified sinewave
Type
12 V / 7 Ah x 1 12 V / 9 Ah x 1
Autonomy time
(full Load)
2 min
Battery
Recharge time (to
90% of rated capacity)
8 h
AC mode
Green LED lighting
Backup mode
Yellow LED flashing
Indicator
Fault
Red LED lighting
Backup mode
Sounding every 10 seconds
Low battery
Sounding every second
Overload
Sounding every 0.5 second
Battery replacement
Sounding every 2 seconds
Acoustic alarm
Fault USP
Continuously sounding
Protection
Discharge, overcharge, and overload protection
Size W x H x D (mm)
100 x 140 x 330
Weight (kg)
6 kg 6,5 kg
Operating temperature
range
0° - 40°C
Relative humidity: 0 – 90 % (non-condensing)
General data
Audible noise
(1 m distance)
< 40 dB (A)
Interfaces
USB and RS232 for status and measurement levels
Communication
Shutdown-Software
(on CD)
Included for all typical operating systems