![](http://pdfasset.owneriq.net/9/29/92976548-a8c5-463b-8b0c-b0bccabf93ff/92976548-a8c5-463b-8b0c-b0bccabf93ff-bg37.png)
Output Connections and Operating Information
55
Figure 4-8. External Trigger Circuit
Figure 4-9. Equivalent Internal OV Trigger Circuit
Power Supply Protection Considerations
Battery Charging
If you are using your supply in a battery charging application, it is recommended that a series protection diode be added to
prevent damage to the supply during an overvoltage shutdown. Remember that each output has an overvoltage protection
circuit that fires a crowbar to disable the output for any of the OVERVOLTAGE conditions described on page 48.
Figure 4-10 illustrates the recommended connections and protection circuit for a battery charging application. The diode
will prevent damage to your supply that can result from excessive battery current flowing into the supply’s output in the
event of an overvoltage shutdown.