American Power Conversion 7500/10000 VA Power Supply User Manual


 
10
NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE, WEB/SNMP CARD, OPTIONAL
SMART SLOT ACCESSORY CARDS OR TERMINAL MODE.
FUNCTION
F
ACTORY
D
EFAULT
U
SER SELECTABLE
CHOICES
DESCRIPTION
High Bypass Point
+10% of
output voltage
setting
+5%, +10%, +15%,
+20%
Maximum voltage that the UPS
will pass to connected
equipment during internal
bypass operation.
Low Bypass Point -30% of output
voltage setting
-15%, -20%, -25%, -30% Minimum voltage that the UPS
will pass to connected
equipment during internal
bypass operation.
Output Voltage 200 V models:
200 VAC
208 V models:
208 VAC
220V models:
220 VAC
230 V models:
230 VAC
200 V models:
200VAC
208 V models:
200, 208, 220, 230, 240
VAC
220V models:
200, 208, 230, 240 VAC
230 V models:
200, 208, 220, 230, 240
VAC
*Use the voltage setting
applicable to your region.
Allows the user to select the
UPS output voltage while
online.
Output Frequency Automatic
(50 ± 3 Hz or
60 ± 3 Hz)
50 ± 3 Hz,
50 ± 0.1 Hz,
60 ± 3 Hz,
60 ± 0.1 Hz
Sets the allowable UPS output
frequency. Whenever possible,
the output frequency tracks the
input frequency.
Number of Battery
Packs
1 Number of Connected
Batteries (four battery
modules per pack)
Defines the number of
connected battery packs for
proper runtime prediction.