American Power Conversion SUA3000XL NETPKG Power Supply User Manual


 
12 Smart-UPS 2200/3000 VA XL 120/208/230 VAC Tower/Rack-Mount 5U User Manual
Low Battery
Warning
PowerChute
software interface
provides automatic,
unattended
shutdown when
approximately two
minutes of battery
operated run time
remains.
2 minutes
LED is located
on rear panel
Brightly
illuminated:
low battery warning
level of about 2 minutes
Dimly illuminated:
low battery
warning level of about
5 minutes
No illumination:
low battery warning
level is about 8 minutes
The low-battery warning beeps are continuous
when two minutes of run time remain.
To change the default interval setting, use a
pointed object such as a pen to press the
VOLTAGE SENSITIVIY switch (rear panel),
while
pressing the button, (front display).
Change the low battery warning interval setting
to the time that the operating system or system
software requires to safely shut down.
Synchronized
Turn-on Delay
0 seconds 0 s
60 s
120 s
180 s
240 s
300 s
360 s
420 s
Specify the time the UPS will wait after the
return of utility power before start up, (to avoid
branch circuit overload).
High Transfer Point 208 V models:
225 VAC
120 V models:
127 VAC
230 V models:
253 VAC
225 VAC
229 VAC
127 VAC
130 VAC
253 VAC
257 VAC
233 VAC
237 VAC
133 VAC
136 VAC
261 VAC
265 VAC
To avoid unnecessary use of the battery where
utility voltage is chronically high, set the high
transfer point higher if the connected
equipment can tolerate this condition.
Low Transfer Point 120 V models:
106 VAC
208 V models:
182 VAC
230 V models:
208 VAC
97 VAC
100 VAC
182 VAC
178 VAC
196 VAC
200 VAC
103 VAC
106 VAC
174 VAC
170 VAC
204 VAC
208 VAC
To avoid unnecessary use of the battery where
utility voltage is chronically low, set the low
transfer point lower if the connected equipment
can tolerate this condition.
Output Voltage
230 V models 230 VAC
220 VAC
230 VAC
240 VAC
Set the output voltage of the UPS.
Function
Factory
Default
User Selectable
Choices Description