APC 3000 Power Supply User Manual


 
32 AIS® 3000 10-30kVA, 208V, Site Preparation and Installation Manual – 990-1957
Input/Output Wiring – Single Mains (default)
The UPS is designed for both single (default) and dual mains installations. Carry out the Total Power
Off Procedure, and follow the below steps to install the UPS in a single-mains installation.
Wiring procedure - single mains
Loosen the (6) M4x13 screws from the plate covering the cable termination area, and remove.
Loosen the (2) M4x13 screws from the top part of the Conduit Box. Loosen the 3 M4x13
attaching it to the bottom part (2 screws in a 13.85in/352mm Enclosure) and remove.
Loosen the (4) M4x13 screws (2 each side) from the bottom part of the Conduit Box and remove.
The illustrations show a 20.59in/523mm Enclosure, but installation procedures are
identical for 13.85in/352mm Enclosures).
N
N
Conduit box
(bottom part)
Conduit box
(top part)
Output
Input
EPO
Conduit
MBP Conduit
Conduit box
(top part)