APC 900 Printer User Manual


 
Page 36
9.0 Specifications
Note: Where specifications ratings differ, values for the 100 Vac version are given in { } brackets,
values for 208 Vac versions are given in ( ) brackets, and values for 220/230/240 Vac versions
are given in [ ] brackets.
9.1 Input
Nominal input voltage: single phase, {100 Vac}, 120 Vac, (208 Vac), [220/230/240 Vac].
Nominal input frequency: 50 or 60 Hz, internally selected by microprocessor.
Input protection, 900VA model: {14 Amp}, 14 Amp, [12 Amp] resettable circuit breaker.
Input protection, 1250VA model:{15 Amp}, 14 Amp, [12 Amp] resettable circuit breaker.
Input protection, 2000VA model: (14 Amp), [15 Amp] resettable circuit breaker.
9.2 Transfer characteristics
Frequency limits for on-line operation: 50 or 60 Hz, ±5%.
Lower input voltage limit for on-line operation: {80 Vac}, 90 Vac, (150 Vac ), [173 Vac;
when set for operation at the nominal 240 Vac line, the lower input voltage limit is
increased to 180 Vac].
Upper input voltage limit for on-line operation: {110 Vac}, 132 Vac, (224 Vac), [253 Vac;
when set for operation at the nominal 240 Vac line, the upper input voltage limit is
increased to 264 Vac].
SmartBoost operation input voltage range: {80 to 90 Vac}, 90 to 103 Vac, (150 to 172 Vac),
[173 to 196 Vac; when set for operation at the nominal 240 Vac line, the SmartBoost input
voltage range is increased to 180 to 204 Vac].
Transfer time: 2 ms typical, 4 ms maximum. Note that 1 ms is 0.001 seconds.
9.3 Output characteristics
Maximum load, 900VA model: 900 VA or 630 W @ 0.70 power factor.
Maximum load, 1250VA model: 1250 VA or 900 W @ 0.72 power factor.
Maximum load, 2000VA model - 100, 120 Vac versions: 2000 VA or 1500 W @ 0.75 power
factor with supplied NEMA L5-30P installed; 1850 VA or 1500 W @ 0.81 power factor
with supplied NEMA 5-20P installed; 1440 VA or 1440 W as supplied. See section 3.0
for maximum load ratings of models with wiring device options.
Maximum load, 2000VA model - 208, 220/230/240 Vac versions: 2000 VA or 1500 W @
0.75 power factor.
On-battery output voltage: {100 Vac}, 115 Vac, (208 Vac), [225 Vac] ±5%. The 220/230/
240 Vac version may be set to provide a nominal 240 Vac, see section 5.0.
On-battery frequency: 50 or 60 Hz, ±0.1 Hz unless synchronized to mains frequency
during utility brownout.
On-battery waveshape: low distortion sinewave.
Protection: overcurrent and short circuit protected, latching shutdown upon overload.