APC 990-2258B-001 Power Supply User Manual


 
4
Remove the two screws
from the cable-inlet at the
front and remove the cable-
inlet plate.
Guide the cable through
the hole in the bottom plate
and up through the cable-
inlet.
Guide the cable through
the side panel hole and run
the cable upwards inside the
panel.
Pull the cable out of the
side panel through the hole
closest to the Network
Management Card area.
Plug the cable into the
probe socket / PowerChute
inlet.
Reattach the cable-inlet
plate (
).
Specifications
Warning: The UPS must be supplied from a 380/220 V,
400/230 V or 415/240 V L1, L2, L3, N, PE, 50 Hz.
AC input
AC output
Battery input
Network
Management
card
10 kVA
UPS ratings 380 V 400 V 415 V
Input frequency (Hz) 40-70 40-70 40-70
Nominal input current (A)
1
13.0 12.3 11.9
Max. input current (A)
2
14.3 13.5 13.1
Input current limit (A)
3
16.8 16.8 16.8
15 kVA 20 kVA
UPS ratings 380 V 400 V 415 V 380 V 400 V 415 V
Input frequency (Hz) 40-70 40-70 40-70 40-70 40-70 40-70
Nominal input current (A)
1
19.4 18.5 17.8 26.0 24.7 23.8
Max. input current (A)
2
21.4 20.3 19.6 28.6 27.2 26.2
Input current limit (A)
3
25.2 25.2 25.2 33.8 33.8 33.8
30 kVA 40 kVA
UPS ratings 380 V 400 V 415 V 380 V 400 V 415 V
Input frequency (Hz) 40-70 40-70 40-70 40-70 40-70 40-70
Nominal input current (A)
1
38.6 36.7 35.3 51.7 49.1 47.3
Max. input current (A)
2
42.5 40.3 38.9 56.8 54.0 52.1
Input current limit (A)
3
50.1 50.1 50.1 66.9 66.9 66.9
10 kVA
UPS ratings 380 V 400 V 415 V
Nominal output current (A) 15.2 14.4 13.9
15 kVA 20 kVA
UPS ratings 380 V 400 V 415 V 380 V 400 V 415 V
Nominal output current (A) 22.8 21.7 20.9 30.4 28.9 27.8
30 kVA 40 kVA
UPS ratings 380 V 400 V 415 V 380 V 400 V 415 V
Nominal output current (A) 45.6 43.3 41.7 60.8 57.7 55.6
UPS ratings
10 kVA 15 kVA 20 kVA 30 kVA 40 kVA
Nominal voltage (V) ± 192 ± 192 ± 192 ± 192 ± 192
External battery fuse (A) 125 125 125 125 125
1.6-1.75 V/cell (automatic, depending on load)