4 APC Step-Down Transformer User Manual
Introduction
Electrical Specifications
Attention:
• Operation above the input voltage range may cause equipment damage.
• Operation below the input voltage range may cause overload or automatic shutdown. When
connecting directly to a branch circuit, check that the line voltage is within specifications. When
connecting to the UPS, check that the line voltage into the UPS is within specifications before
transferring to bypass mode.
Note: In order for AP9626 models to output the full 5000 VA, the input must be hardwired to a 5500 VA source.
*For continuous operation below Vin = 205 Vac, the output load must be reduced to limit the maximum input
current to the amount specified above. Continuous operation above the maximum specified input current may
cause the unit to overheat and shut down. Please contact APC for additional information.
** Not available for AP9627.
Installation With Line Cord
(AP9826 or AP9627)
With Hardwire
(AP9626 or AP9628)
Nominal Input Voltage
208 Vac
Nominal Output Voltage
120 Vac
Input Voltage Range
185-230 Vac*
Input Current Rating
24 A 26 A
Line Frequency
60 Hz
Efficiency
90-95%
Maximum Input Power
5000 VA 5500 VA
Maximum Output Power
4500 VA 5000 VA
Model AP9626 AP9627 AP9628
Input Power
Distribution
3 ft cord with L6-30P or
hardwired
2 ft cord with L6-30P Hardwire
Output Power
Distribution
(2) 15 A circuits with
(4) 5-20R and (2) 15 A circuits
with (2)5-20R
(4) 20 A circuits with
(4) L5-20R
Hardwire