APC GLF50KF Power Supply User Manual


 
Heat Rejection
The MGE Galaxy 4000 UPS cabinets generate heat and exhaust air through the top portion of its
enclosures. Air intake is through the bottom and front of the cabinet. All other cabinets are convection
cooled. To assist you in planning for your HVAC needs, heat rejection data is provided in table below.
The cabinet airow and recommended top clearance are provided in “Cabinet Placement“ section.
The MGE Galaxy 4000 is intended for use in an environment where control of temperature and
humidity is provided.
Heat Rejection Data @ 208/208 VAC
UPS Cabinet 40 kVA 50 kVA 65 kVA 75 kVA
BTU/Hr 14,900 18,700 24,200 28,000
Note: To provide for adequate ventilation, a minimum of 36 inches clearance should be
maintained above the top of the MGE Galaxy 4000 cabinet.
Cabinet Clearances
The MGE Galaxy 4000 UPS cabinet top clearance of 36 inches for fan exhaust is recommended.
Additionally, adequate space must be included in the front and top of each cabinet (approx. 36 inches)
to allow the doors/panels of the cabinet to be opened for service and maintenance procedures.
For an installation where seismic requirements must be met, additional clearance at the side of the
cabinet must be included to accommodate the seismic anchors. Contact the Customer Support Center
to order.
Preparation for Storage
If the equipment is to be stored prior to installation, it should be stored in a cool, dry, well-ventilated
location that is protected against rain, splashing water, chemical agents, etc. The equipment should
be covered with a tarpaulin or plastic wrapper to protect it against dust, dirt, paint, or other foreign
materials. See the section of this manual titled "Environmental Recommendations" for recommended
storage environmental conditions.
Note: Batteries should be stored no longer than three (3) months at 25°C (77°F) or lower
prior to recharging. Exceeding the recommended ambient storage temperature will
reduce battery back-up time and may adversely affect battery life.
990–3964–001
MGE Galaxy 4000 40–75 kVA 208 V
7