APC PMH3XS-B Surge Protector User Manual


 
Installation and Operation Manual 5
Table 1:
SPD Per Phase I
2
tI
apparent
I
p
I
th
PM_3XS-B 175 kA
2
seconds 17,000 A RMS 40,000 A RMS 220 A
CAUTION
LOSS OF SURGE SUPPRESSION
Do not energize the SPDs until the electrical system is completely
installed, inspected, tested, and all conductors have been connected
and functional, including the neutral.
Verify the voltage rating of the device and system before energizing
the SPD.
Disconnect the SPD, including the neutral, from the power source
before performing high-potential insulation testing or any tests where
SPD components will be subjected to voltages higher than their rated
turn-on voltage.
Failure to follow these instructions can result in injury or equipment
damage.
Precautions