APC SMX2200RMHV2U Power Supply User Manual


 
11Smart-UPS X 2000/2200/3000 VA
Switched Outlet Groups
Overview
The Switched Outlet Groups can be configured to independently turn off, turn on, shut down, put to
sleep, and reboot connected equipment.
The Switched Outlet Groups can be commanded to do the following:
Turn off: Disconnect from power immediately and restart only with a manual command
Turn on: Connect to power immediately
Shutdown: Disconnect power in sequence, and automatically reapply power in sequence when
utility power becomes available
Reboot: Shut down and restart
Sleep: Reboot after a long delay
In addition, the Switched Outlet Groups can be configured to do the following:
Turn on or off in a specified sequence
Automatically turn off or shut down when various conditions occur
Note: Whether the Switched Outlet Groups are configured or not, all of the outlets provide
battery back-up power.
Using the Switched Outlet Groups
1. Connect critical equipment to a Switched Outlet Group.
2. Connect peripheral equipment to the other Switched Outlet Groups.
During a power outage, to conserve battery runtime, non-essential equipment can be
configured to shut down after a short delay
If equipment has dependent peripherals that must restart or shut down in a specific order, such
as an ethernet switch that must restart before a connected server, connect the devices to
separate groups
Equipment that needs to reboot independently from other equipment should be added to a
separate group
3. Use the Configuration menus to configure how the Switched Outlet Groups will react in the event
of a power outage.
Customize the Switched Outlet Groups
Use the Control menus to customize the Switched Outlet Groups.
Function Factory Default Options Description
Name String
Outlet Group
Outlet Group 1, 2, 3
Edit these names using an external interface, such as the Network
Management Card Web interface.
UPS Name String APC UPS
Turn On Delay 0 sec Set the value in
seconds
The amount of time the Switched Outlet Groups
will wait between receiving the command to turn
on and the actual startup.