APC SU700RM2U Power Supply User Manual


 
Input
Nominal input voltage 120 V
Input frequency 50/60 Hz +/- 3 Hz (auto sensing)
Input Connection Type
 
Cord Length 8 feet (2.44 meters )
Input voltagerangefor main operations 82 - 144 V
Input voltageadjustable rangeformain
operations
75 - 154 V
Surge Protection and Filtering
Surge energy rating 459 joules
Filtering
Full time multi-pole noise filtering: 0.3% IEEE surge let-through: zero
clamping response time : meets UL 1449
Runtime
Typical backup time
at half load
18.6 minutes (225 Watts)
Typical backup time
at full load
5.8 minutes (450 Watts)
Runtime Chart Smart-UPS
Batteries
Battery type
Maintenance-freesealed Lead-Acid battery with suspendedelectrolyte :
leakproof
Replacementbattery cartridge (1) RBC22
Physical
Maximum height dimensions 3.50 inches ( 8.89 cm )
Maximum width dimensions 19.00 inches ( 48.26 cm )
Maximum depth dimensions 18.00 inches ( 45.72 cm )
Net weight 48.00 lbs. ( 21.82 kg )
Shipping Weight 55.25 lbs. ( 25.11 kg )
Shipping Height 9.88 inches ( 25.10 cm )
Shipping Width 23.38 inches ( 59.39 cm )
Shipping Depth 23.75 inches ( 60.33 cm )
Color Beige
UPC Code 731304013693
Environmental
OperatingEnvironment 0 - 40 °C (32 - 104°F)
OperatingRelativeHumidity 0 - 95%
OperatingElevation 0-10000 feet (0-3000 m)
Storage Temperature -15 - 45 °C (5 - 113°F)
Storage RelativeHumidity 0 - 95% Non-condensing
Storage Elevation 0-50000feet (0-15000 m)
Online thermal dissipation 68 BTU/hr
Conformance
Approvals CSA, FCC Part 15 Class A, UL 1449, UL 1778
Standard warranty
2 years repairor replace, optional on-site warrantiesavailable, optional
extended warrantiesavailable
Equipment protection policy Lifetime: $150000
* Without TAX/VAT
      
 
Copyright ©American Power Conversion Corp., all rights reserved
! "  " ## "  " 
!  $% "  " % %