APC SUA5000RMT5U Computer Hardware User Manual


 
990-3239A 7/2008
Installation Guide Smart-UPS I/O Hardwire Kit
AC Input
Connector
Primary
Ground
(Green Wire)
Ground
Input Line1
(Hot)
Output Line1
Input Line2
(or Neutral)
Output Line2
(or Neutral)
AC Input
Connector
AC Input
Connector
Remove the screws that secure the PDU panel to the UPS.
Save these screws for securing the I/O hardwire panels.
Disconnect the PDUcables as shown in the diagram.
Remove the screws that secure the I/O panel to the
UPS.
Save these screws for securing the I/O hardwire
panels.
Disconnect the input cable
Secure the terminal block and label to the UPS as shown in the
diagram, using two screws (supplied).
Secure the output panel to the UPS using two screws,
(screws and panel supplied).
The top edge of the blank panel fits behind the output panel.
Secure the blank panel to the UPS using four screws supplied.
Connect input and output wires as shown in diagram.
Connect the terminal block and UPS connectors as shown in diagram.
Secure the hardwire input panel (supplied), to
the UPS using two of the screws removed from
the PDU panel.
Install appropriate strain relief clamps
(not supplied), to the input panel (not supplied),
as shown in the diagram.
2200/3000XL 120/208/230 V models
The PDU and AC input/output panels on the 2200/3000 VA rack-mount units vary in appearance. The hardwire panels and hardwiring configurations for the 2200/3000 VA rack-mount units are identical.
NOTE: The input and
output cables may be
connected to the
terminal block prior
to installing the panels
and the terminal block
in the UPS.